Data Report - netvox R718N1 User Manual

Wireless 1-phase current meter
Hide thumbs Also See for R718N1:
Table of Contents

Advertisement

5. Data Report

The device will immediately send a version packet report along with an uplink packet including current, multiplier and battery
voltage.
Default setting:
Maximum time: Max Interval =30 min (1800s)
Minimum time: Min Interval =30 min (1800s) (Check the current voltage once per Min Interval)
CurrentChange:0x0064 (100mA)
Note:
The data transmission period of the device is subject to the programming configuration.
If the minimum time of report configuration is less than 30 seconds, all counted as 30 seconds.
If the maximum time of report configuration is less than minimum time, all counted as minimum time.
The device starts sampling 15 seconds before the minimum time is due and lasts for 15 seconds.
If the current changes frequently, the sampling result may be inaccurate.
Press function key to trigger.
For the analysis of the data reported by the device,
refer to the Netvox LoraWAN Application Command document and http://www.netvox.com.cn:8888/page/index.
Data report configuration and sending period are as following:
Min. Interval
(Unit:second)
Any number between
30~65535
Max. Interval
(Unit:second)
Any number between
Min.~65535
Reportable Change
Can not be 0.
5
Current Change≥
Reportable Change
Reportable Change
Report
per Min. Interval
Current Change<
Report
per Max. Interval