Advertisement

5.Data Report

After power on, the device will immediately send a version packet report and an attribute packet report.
The device sends data according to the default configuration before any other configuring.
Default Setting:
Maximum time: 900s (15min)
Minimum time: 900s (15min)
Battery Change: 0x01 (0.1V)
Current Chang:0x02 (2mA)
Note:
1. The cycle of the device sending the data report is according to the default.
2. The interval between two reports must be the MinTime
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/page/index
Data report configuration and sending period are as following:
Min. Interval
(Unit:second)
Any number between
1~65535

5.1 Example of ReportDataCmd

FPort:0x06
Bytes
1
Version
Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
to resolve uplink data.
Max. Interval
(Unit:second)
Any number between
1~65535
1
DeviceType
ReportType
Reportable Change
Can not be 0.
1
5
Current Change≥
Reportable Change
Report
per Min. Interval
Var(Fix=8 Bytes)
NetvoxPayLoadData
Current Change<
Reportable Change
Report
per Max. Interval