4.7

Recommended External Fuses

External fuses should be chosen based upon the physical manifold configuration. Please refer to table below for
the fuse sizing chart.
External Fuse Sizing Chart
Number of Solenoid Valve Coils Energized Simultaneously
The Node Power pins supply power to the node electronics. These pins must be powered at all
N O TE!
times for the communication node to be functional. See page 4-15 for reference.
Reverse polarity protection is provided.
Distributed by Valin Corporation | www.valin.com | (800) 774-5630 | customerservice@valin.com
580 EtherCAT
Power Consumption - Power Connector Pin for VALVES
Description
___ X 0.03 A (501 Series)
___ X 0.05 A (502 Series)
___ X 0.07 A (503 Series)
Suggested External +24 VDC (Valves) Fuse Value:
Power Consumption – Power Connector Pin for NODE
Description
Communication Node Power Consumption
Suggested External Pin +24 VDC (Node) Fuse Value:
TD580ECTM1-3EN
Subject to change without notice
www.emerson.com
TM
Technical Manual
=
=
=
Total:
Surge Compensation:
X
=
Surge Compensation:
X
=
09/2021
Current
__________Amps
__________Amps
__________Amps
__________Amps
1.25
__________Amps
Current
0.110 Amps
1.25
0.1375 Amps
4-19