1.4 Controller Setup

Use a personal computer (PC) running the ATS
Controller Setup Program to set the address and baud
rate of the Modbusr network interface port. Refer to the
Setup Program Operation Manual for instructions for
using the program, including creating data windows.
Use the Network Interface Port data window to view and
set the address and baud rate of the Modbusr network
interface port to match the other devices in the network.
See Figure 1-5.
1.4.1
Network Interface Port Display
Window
View the address and baud rate of the Modbusr network
interface port.
1.4.2
Network Interface Port Setup
Window
Set up the Modbusr network interface port to
communicate with the other devices in the network. See
Figure 1-6.
Modbusr is a registered trademark of Schneider Electric.
TP-6208 4/03
Choose a unique network address for each device in the
network. Type in the address or use the up and down
arrows. Choose the baud rate from the drop-down list.
Allowable baud rates are 9600 and 19200 baud. Select
the baud rate to match the other devices on the network.
Figure 1-5 Network Interface Port
Figure 1-6 Network Interface Port Setup
Section 1 Controller Connection and Setup
3