Register
Data Description
40750
Before Transfer to Source 1 Mtr Load Discon.
Output
40751
Before Transfer Source 1 Delay #1
40752
Before Transfer Source 1 Delay #2
40753
Before Transfer Source 1 Delay #3
40754
Before Transfer Source 1 Delay #4
40755
Before Transfer Source 1 Delay #5
40756
Before Transfer Source 1 Delay #6
40757
Before Transfer Source 1 Delay #7
40758
Before Transfer Source 1 Delay #8
40759
After Transfer to Source 1 Mtr Load Discon.
Output
40760
After Transfer Source 1 Delay #1
40761
After Transfer Source 1 Delay #2
40762
After Transfer Source 1 Delay #3
40763
After Transfer Source 1 Delay #4
40764
After Transfer Source 1 Delay #5
40765
After Transfer Source 1 Delay #6
40766
After Transfer Source 1 Delay #7
40767
After Transfer Source 1 Delay #8
40768
Before Transfer to Source 2 Mtr Load Discon.
Output
40769
Before Transfer Source 2 Delay #1
40770
Before Transfer Source 2 Delay #2
40771
Before Transfer Source 2 Delay #3
40772
Before Transfer Source 2 Delay #4
40773
Before Transfer Source 2 Delay #5
40774
Before Transfer Source 2 Delay #6
40775
Before Transfer Source 2 Delay #7
40776
Before Transfer Source 2 Delay #8
40777
After Transfer to Source 2 Mtr Load Discon.
Output
40778
After Transfer Source 2 Delay #1
40779
After Transfer Source 2 Delay #2
40780
After Transfer Source 2 Delay #3
40781
After Transfer Source 2 Delay #4
40782
After Transfer Source 2 Delay #5
40783
After Transfer Source 2 Delay #6
40784
After Transfer Source 2 Delay #7
40785
After Transfer Source 2 Delay #8
40800--
Common Event Alarms
40864
40900
Plant Exerciser Mode
40901
Length Push Button Exercise
40902
Time of Push Button Exercise
40903
Initial Date of Push Button Exercise
40905
Enabled / Loaded / Interval Code / Repeat Rate
/
Next Cal. Event
C
10
Section 2 Modbus Registers
/
/
p
Data Type
Access
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word
0--3600 Sec
RW
Word * 65
0--14: Event code of defined common alarm
[
[0:15]
]
(DCA) (see Section 2.5)
15: 0=Not assigned to DCA; 1= Assigned to DCA
RW
Word
0 = Push Button Mode; 1 = Calendar Only; 2 =
Calendar w/ Override
RW
Word
1--5999 Minutes
RO
Word
Minutes since midnight
RO
Word [0:15]
[
]
0--4: Day of Month
5--8: Month of Year
9--15: Year + 2000 (2000--2127)
RW
Word[0:8]
[
]
0: 0 = Disabled; 1 = Enabled
1: 0 = Unloaded; 1 = Loaded
2--3: Interval Code ( 00 = DMO; 01 = day; 10 =
week; 11 = month )
4--7: Repeat Rate ( 1--12 )
8: 0 = Not Running; 1 = Running (read only)
Range/Units
TP-6208 4/03