BATTERY HIGH RESISTANCE
BATTERY HIGH VOLTAGE FAULT
BATTERY INTERNAL FAULT
BATTERY LOW VOLTAGE
Notifier INSPIRE E10/E15 Control Panels - Commissioning
Meaning and possible remedial action.
If a fault persists then seek advice. Any remedial action requiring wiring
or replacement of parts, this work must be done by a trained engineer.
Battery with high resistance has been detected.
Caution: Battery may heat up on load resulting in
battery voltage drop.
Action: Check battery temperature, charger module
LED indication and connection to battery terminals. If
the fault persists then replace battery.
Battery high voltage has been detected.
Note in a cold environment the battery charge voltage
may be slightly higher than normal.
Action: Check the environment around the panel and
ensure it is within the specified range and also check
the battery charger voltage.
An internal battery fault has been detected.
Action: Check the battery and wiring. If the fault
persists then replace battery.
The battery charge level has run low or there is a fault
with the battery or charging circuit, the battery may be
discharged.
Action: Check mains supply is present and the charger
circuit is working correctly, allow battery to recharge if
necessary.