Honeywell NOTIFIER INSPIRE E10 Commissioning Instructions page 31

Fire alarm control panels
Hide thumbs Also See for NOTIFIER INSPIRE E10:
Table of Contents

Advertisement

Message
NO REPLY
TOO MANY DEVICES DETECTED
Notifier INSPIRE E10/E15 Control Panels - Commissioning
Meaning and possible remedial action.
If a fault persists then seek advice. Any remedial action requiring wiring
or replacement of parts, this work must be done by a trained engineer.
The panel is no longer able to communicate with a
device.
Action: Check that the device is correctly fitted and
ensure wires are secured to the device terminals. If the
fault persists then replace the device.
Too many devices detected on a loop circuit.
Action: Check and ensure the maximum number of
devices allowed on a loop circuit are not exceeded.