Messages and their Meanings
Message
NO CONFIRMATION SIGNAL RECEIVED
SELF TEST FAILED
SUBSYSTEM INITIALIZATION IN PROGRESS
PROCESSOR RELATED FAULTS
CO PROCESSOR SYSTEM FAULT
FIRMWARE FAULT
20
Meaning and possible remedial action.
If a fault persists then seek advice. Any remedial action requiring wiring
or replacement of parts, this work must be done by a trained engineer.
Confirmation signal not received within time limit.
Action: TBA.
Self-test has failed, the loop device did not pass a
self test or did the self test which was not completed.
Action: Replace the device.
Sub-system is still initializing and the system is not
ready to respond to command or request.
Action: Wait and let the sub-system initialise.
Indicates fault on the backup processor of ID2net or
PIC in S200 or an issue during communication with
FAT co-processor
Action: Reboot and if the fault persists then replace the
affected hardware.
A problem has been found with the execution of the
firmware, for example a task monitoring problem.
Action: Check and ensure compatible firmware is
loaded on the panel build.