Mounting the transmitter
WARNING
Process connection temperatures above +185 °F (+85 °C) require a
limited ambient temperature, reduced by a 1:1.5 ratio.
Consider process connection and ambient temperatures when
installing the 3051 with hazardous location certifications. See
2-1.
Table 2-1: Intrinsically safe/increased safety
Process connection temperature
-76 to +185 °F (-60 to +85 °C)
+185 to +250 °F (+85 to +121 °C)
(1)
Maximum ambient temperature is reduced by a ratio of 1:1.5 as process
connection temperature increased beyond +185 °F (+85 °C).
2.1
Mount the transmitter in a liquid flow application
Procedure
1. Place taps to the side of the line.
2. Mount the transmitter beside or below the taps.
Quick Start Guide
Maximum ambient temperature
+158 °F (+70 °C)
+158 to +320 °F (+70 to +160 °C)
Quick Start Guide
Table
(1)
5