Emerson Rosemount 3051 Operating Instructions Manual page 26

Pressure transmitter
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Quick Start Guide
7.1.3  Zero trim using the transmitter zero adjustment buttons
You can use the transmitter zero adjustment buttons to set the lower
range value (LRV) to the pressure applied to the transmitter.
This adjustment will affect the 4–20 mA value only. To perform a
rerange using the zero adjustment buttons:
Procedure
1. Loosen the certifications label screw and slide the label to
expose the zero adjustment buttons.
2. Set the 4 mA point by pressing the Zero button for two
seconds. Verify the output is 4 mA.
The optional LCD display will show
Figure 7-1: Zero adjustment or Quick Service buttons
26
December 2023
.
ZERO PASS
Emerson.com

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3051cf

Table of Contents