Connections Block Diagram; Terminal Arrangement; Input Circuits; Input Connections - Omron H5CZ Manual

Digital timer
Hide thumbs Also See for H5CZ:
Table of Contents

Advertisement

H5CZ
Connections
Block Diagram
Output circuit
(Basic insulation)

Input circuits

Note: Basic insulation is provided between the power supply circuit and the input circuits. However, basic insulation is not provided in the
H5CZ-@D.

Terminal Arrangement

Confirm that the power supply meets specifications before use.
Signal
4
5
Reset
3
6
2
7
1
8
0V
(-)
(+)
Note: Do not connect unused terminals as relay terminals.
Input Circuits
Signal and Reset Input
No-voltage Inputs (NPN Inputs)
+14 V
1 kΩ
Internal
IN
circuit

Input Connections

The inputs are no-voltage (closed or open). (The H5CZ-L8E@ does not have an input.)
No-voltage Inputs (NPN Inputs)
Open Collector
PLC or
sensor
1
3
4
Note: Operate with transistor ON
No-voltage Input Signal Levels
Short-circuit level Transistor ON
• Residual voltage: 3 V max.
• Impedance when ON: 1 kΩ max.
No-contact
(The leakage current is approx. 12 mA when the
input
impedance is 0 Ω.)
Open level Transistor OFF
• Impedance when OFF: 100 kΩ min.
Contact input
Use contacts which can adequately switch 5 mA at 10 V
Note: The DC voltage must be 30 VDC max.
6
(Basic insulation)
Power supply
circuit
(See note.)
Display circuit
Internal control
circuit
Key switch circuit
H5CZ-L8/-L8D
Internal circuit
Contact
output
Terminals 1 and 2 of the H5CZ-L8D
are connected internally.
Voltage Output
Sensor
1
3
4
Note: Operate with transistor ON
H5CZ-L8E/-L8ED
Internal circuit
4
5
3
6
Instantaneous
contact output
2
7
OUT1
1
8
(–)
(+)
Contact Input
1
3
4
Note: Operate with relay ON
• Leakage current: 1.5 mA max.
• Switching capacity: 5 mA min.
• Residual voltage: 3.0 VDC max.
• Operating voltage: 10 VDC
Internal circuit
Time-limit
contact output
OUT2
DC Two-wire Sensor
1
3
4
Note: Operate with transistor ON
Applicable Two-wire Sensor

Advertisement

Table of Contents
loading

Table of Contents