H5CZ
Timer
Explanation of Functions
Operating Procedures for Timer Function
Time Range (timr)
Set the range to be timed in the range 0.001 s to 9,999 h.
Timer Mode (timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode.
In UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
Output Mode (outm)
Set the output mode.
The possible settings are A, A-1, A-2, A-3, b, b-1, d, E, F, Z and S.
(For details on output mode operation, refer to "Timing Charts" on
page 16.)
Output Time (otim)
When using one-shot output, set the output time for one-shot output
(0.01 to 99.99 s).
One-shot output can be used only if the selected output mode is A,
A-1, A-2, A-3, b, b-1 or S.
If the output time is set to 0.00,
held.
Input Signal Width (iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal and
reset inputs.
The same setting is used for all external inputs (signal and reset
inputs).
If contacts are used for the input signal, set the input signal width to
20 ms.
Processing to eliminate chattering is performed for this setting.
Key Protect Level (kypt)
Set the key protect level.
Refer to "Key Protect Level" on page 28.
Instantaneous/Time-limit (otmd)
Set the contact output to time-limit SPDT + instantaneous SPDT or
time-limit SPDT operation.
14
hold
is displayed, and the output is
Set Value Upper Limit (sl-h)
Set the upper limit for the set value when it is set in Run Mode.
The limit can be set to between 1 and 9999.
This setting does not apply to the ON duty in Z mode.
Output ON Count Alarm Set Value (on-a)
Set the alarm value for the output ON count.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of the output exceeds the alarm set value,
be displayed on the Timer to indicate that the output ON count alarm
value was exceeded. Refer to "Self-diagnostic Function" on page
e3
28 for information on the
display.
ON Count Alarm Set Values for Outputs 1 and 2 (OUT1
and OUT2) (on1a and on2a)
Set the ON count alarm values for the outputs 1 and 2.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of instantaneous output 1 or 2 exceeds the alarm
e3
set value,
will be displayed on the Timer to indicate that the output
ON count alarm value was exceeded. Refer to "Self-diagnostic
Function" on page 28 for information on the
Output ON Count Monitor Value (on-c)
The monitor value is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
ON Count Monitor Values for Outputs 1 and 2 (OUT1 and
OUT2) (on1c and on2c)
The monitor value for output 1 or 2 is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
e3
will
e3
display.