H5CC
Digital Timer
INSTRUCTION MANUAL
EN
Thank you for purchasing the OMRON Product.
To ensure the safe application of the Product, read this
manual carefully before using the Product and always
keep it close at hand when the Product is in use.
OMRON Corporation
©All Rights Reserved
3616492-6 (Side-A)
For details, refer to the latest datasheet (L220-E1).
SUITABILITY FOR USE
Omron Companies shall not be responsible for conformity with any standards, codes
or regulations which apply to the combination of the Product in the Buyer's
application or use of the Product. At Buyer's request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which
apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product,
machine, system, or other application or use. Buyer shall be solely responsible for
determining appropriateness of the particular Product with respect to Buyer's
application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
Mounting and Panel-cutout Dimensions Diagram
)
Mounting Dimensions (Unit: mm
Front panel dimensions
Flush Mounting
are the same for all
H5CC-A11
/-L8
models.
Y92S-P6 (order separately)
Waterproof Packing
Y92F-30 (order separately)
H5CC
TIMER
Panel
Flush Mounting Adapter
48
(48)
48
P3GA-11/P3G-08 (order separately)
Back-connecting Socket
7.5
89.9
Surface Mounting
H5CC-A
/AS
/AU
H5CC-A11
/L8
Y92S-P6 (provided)
Y92F-30 (provided)
Waterproof Packing
Flush Mounting Adapter
Panel
103.2
100.9
*
(48)
P2CF-08 (-E)/ P2CF-11(-E)
(order separately)
Front-connecting Socket
* These dimensions vary with
7.5
57.5
the type of DIN track
(reference value).
Step1
The H5CC is a Timer that contains more than
one functional timer. Use the following chart to
enter configuration selection mode and then
refer to Table 1 and set the functions that are
suitable to the application.
Operation as a Timer
Step2
Note: Refer to the datasheet for detailed parameter settings.
Change from RUN Mode to Function Setting Mode.
Set the parameters using the UP Key or DOWN Key.
The characters displayed in reverse video are the default settings.
Press UP1+UP3 keys once to move to the previous parameter.
Press DW1+DW3 keys once to move to the next parameter.
Display
Parameter name
Set value
※
Time range
1
timr
UP/DOWN mode
,
timm
up
down
Output mode
,
,
,
,
,
outm
a
a-1
a-2
a-3
b
/ 0.01 ~ 99.99
Output time
otim
hold
Input signal width
,
iflt
20ms
1ms
NPN/PNP input mode
,
imod
npn
pnp
Instantaneous/time-limit
,
otmd
1c1c
2c
1 ~
Set value upper limit
sl-h
999999
Key protect level
,
,
,
kypt
kp-1
kp-2
kp-3
kp-4
□
□
H5CC-AU
and H5CC-L8E
Output 1 inversion
,
ot1i
n-o
n-c
Output 2 inversion
,
ot2i
n-o
n-c
Indicator display mode
,
,
indc
on
alof
allt
0 ~
~ 9999
on1a
Output 1 (OUT1) ON count alarm set value
100
0 ~
~ 9999
on2a
Output 2 (OUT2) ON count alarm set value
100
-
on1c
Output 1 (OUT1) ON count monitor value
-
on2c
Output 2 (OUT2) ON count monitor value
0.0 ~
~ 99.9
Total run time alarm set value
ot-a
10.0
-
Total run time monitor value
ot-c
-
Software version
ver
□
□
Models Other Than H5CC-AU
and H5CC-L8E
Output inversion
,
ot-i
n-o
n-c
Indicator display mode
,
,
indc
on
alof
allt
0 ~
~ 9999
Output ON count alarm set value
on-a
100
-
Output ON count monitor value
on-c
0.0 ~
~ 99.9
Total run time alarm set value
ot-a
10.0
-
Total run time monitor value
ot-c
-
Software version
ver
*1 The set values for the time range are as follows:
Display in RUN mode
(other than Z mode).
Display
Set value
~
0.01s
9999.99s (default setting)
----.--
s
~
-----.-
0.1s
99999.9s
s
~
1s
999999s
------
s
~
--:--:--
0h0min01s
99h59min59s
hms
~
0.1min
99999.9min
-----.-
m
~
------
1min
999999min
m
~
0h01min
9999h59min
----:--
hm
~
-----.-
0.1h
99999.9h
h
~
1h
999999h
------
h
~
---.---
0.001s
999.999s
s
Key-protect Switch Settings
When the key-protect switch is ON,
ON (enable)
ON (enable) individual key
operations can be disabled to
OFF (disable)
prevent setting errors according to
(Factory setting)
the key protect levels (KP-1 to
KP-7) shown in the following table.
Note: Key protect levels are set in
function setting mode.
Key protect
indicator
SAFETY PRECAUTIONS
Keys to Warning Symbols
Indicates a potentially hazardous situation which, if not
CAUTION
avoided, is likely to result in minor or moderate injury or in
property damage.
CAUTION
Do not allow pieces of metal, wire clippings, or fine metallic shavings or fillings
from installation to enter the product. Doing so may occasionally result in
electric shock, fire, or malfunction.
Do not use the Timer where subject to flammable or explosive gas. Minor
injury due to explosion may occasionally occur.
Fire may occasionally occur. Tighten the terminal screws to the rated torque.
H5CC terminals and P3GA-11/P3G-08 Socket terminals: 6.55 to 7.97 lb-in (0.74
to 0.90 N·m)
P2CF Socket terminals: 4.4 lb-in (0.5 N·m)
Do not touch any of the terminals while power is being supplied. Be sure to
mount the terminal cover after wiring. Minor injury due to electric shock may
occasionally occur.
The life expectancy of the output relay varies considerably according to its
usage. Use the output relay within its rated load and electrical life expectancy.
If the output relay is used beyond its life expectancy, its contacts may become
fused or there may be a risk of fire. Also, be sure that the load current does not
exceed the rated load current and when using a heater, be sure to use a
thermal switch in the load circuit.
Do not disassemble, modify, or repair the Timer or touch internal components.
Minor electric shock, fire, or malfunction may occasionally occur.
Precautions for Safe Use
) When mounting the Timer to a panel, tighten the two mounting screws alternately, a little
1
at a time, so as to keep them at an equal tightness. If the panel screws are tightened
unequally, water may enter the panel.
) Store the Timer at the specified temperature. If the Timer has been stored at a
2
°
temperature of less than -10
C, allow the Timer to stand at room temperature for at least
3 hours before use.
) Mounting the Timer side-by-side may reduce the life expectancies of internal components.
3
Power supply voltage
Panel-cutout Dimensions
Diagram (Unit: mm)
Allowable voltage fluctuation range 85% to 110% of rated supply voltage (12 to 48
Power consumption
Standard panel cutout is shown in the
following diagram. (conforms to DIN 43700)
A space of 15 mm or greater (a panel cut-out
distance of 60 mm or greater) is
Operating temperature range
recommended towards the Adapter's hook
Storage temperature range
side to enable easier mounting work.
Operating humidity range
Altitude
Recommended fuse
Weight
Installation environment
Input method
No-voltage input
48
1. The thickness of a mounting panel
should be 1 to 5 mm.
2. It is possible to mount Timers
side-by-side. (But only towards the
non-hook side.)
1
2
3
7
n Units mounted
side-by-side
10
A
Display Section
1
A (48n 2.5)
0
1. Key Protect Indicator
2. Control Output Indicator
3. If the products are mounted side by
side, water resistance will be lost.
3. Reset Indicator
Reset operation is ON.)
4. Present Value Display (Main Display)
Package Contents
height: 10 mm (white)
5. Time Unit Indicators
• Digital Timer
min, 0.0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators
flash to indicate timing operation.)
• Instruction manual (this document)
6. Set Value Display (Sub-display)
• Mounting Adapter, Waterproof
mm (green)
Packing, Terminal Cover (except
7. Set Value 1, 2 Indicator
H5CC-A11
/L8
)
Operation Key
8. UP Keys (UP1 to UP6)
(UP 1, 2, 3, 4, 5 and 6 from right to left)
Operating Procedures
Configuration selection mode
Power ON
UP1+UP6 or DW1+DW6 (2 s min.)
func
Run mode
tim
UP1+UP6 or DW1+DW6 (2 s min.)
UP1+UP3 or DW1+DW3
(2 s min.)
Function setting mode
Power ON
Run mode
UP1+UP3 or DW1+DW3
(2 s min.)
Comments
-
-
,
,
,
,
,
,
,
,
,
Only modes
,
,
, and
can be selected for H5CC-L8E
b-1
b-5
c
d
e
f
g
h
z
s
a-2
b
e
z
(If the output time is set to 0.00, hold is displayed.)
Displayed for modes
,
,
,
,
,
and
only. Unit: second
a
a-1
a-2
a-3
b
b-1
s
□
Displayed only for models other than H5CC-L8E
and H5CC-A11F.
□
Displayed only for models other than H5CC-L8
and H5CC-A11F.
Displayed only for the H5CC-L8E
.
-
-
,
,
,
kp-5
kp-6
kp-7
-
-
-
×
1,000
×
1,000
The monitor value is only displayed. It cannot be set.
The monitor value is only displayed. It cannot be set.
Unit: year
The Total run time monitor value is only displayed. It cannot be set.
The software version is only displayed. It cannot be set.
-
-
×
1,000
The monitor value is only displayed. It cannot be set.
Unit: year
The Total run time monitor value is only displayed. It cannot be set.
The software version is only displayed. It cannot be set.
Display in RUN mode. (Z mode)
12.34
Present value
1234
Present value
10
ON duty
* UP1+UP3 or
Set Value
2000
DW1+DW3
12.34
Present value
18.50
Cycle time
* Each time the UP1+UP3 or DW1+DW3 Key are
pressed, the set value display (6) will switch
between ON duty and Cycle time.
*Mode
Display switch
Reset
UP/DOWN
Level
change
in the run mode
operation
Key
KP-1
Invalid
Valid
Valid
Valid
(default setting)
Valid
Invalid
Valid
KP-2
Invalid
KP-3
Invalid
Valid
Valid
Invalid
KP-4
Invalid
Valid
Invalid
Invalid
KP-5
Invalid
Invalid
Invalid
Invalid
KP-6
Invalid
Invalid
Valid
Valid
KP-7
Invalid
Invalid
Invalid
Valid
* Changing mode to configuration selection mode or
function setting mode.
) Use the Timer within the specified ranges for the ambient operating temperature and humidity.
4
) Do not use or store the product in the following locations:
5
• Locations subject to sudden or extreme changes in temperature.
• Locations where high humidity may result in condensation.
• Locations with excessive vibration or shock.
• Locations subject to water.
• Locations subject to oil.
• Locations prone to icing.
• Locations subject to exposure chemicals.
• Locations subject to bugs and small animals.
) Do not use this Timer in dusty environments, in locations where corrosive gasses are
6
present, or in locations subject to direct sunlight.
) Install the Timer well away from any sources of static electricity, such as pipes
7
transporting molding materials, powders, or liquids.
) Internal elements may be destroyed if a voltage outside the rated voltage range is applied.
8
) Be sure that polarity is correct when wiring the terminals.
9
) Separate the Timer from sources of noise, such as devices with input signals from power
10
lines carrying noise, and wiring for I/O signals.
) Do not connect more than two crimp terminals to the same terminal.
11
) Up to two wires of the same size and type can be inserted into a single terminals.
12
) Use the specified wires for wiring.
13
Applicable Wires: AWG 18 to AWG 22, solid or twisted, copper
Wiring stripping length: 5 to 6 mm (recommended)
) Install a switch or circuit breaker that allows the operator to immediately turn OFF the
14
power, and label it to clearly indicate its function.
When the Timer other than H5CC-A11F is operated with no-voltage input (NPN input),
15)
approximately 14 V is output from the input terminals. Use a sensor that contains a diode.
) Use a switch, relay, or other contact so that the rated power supply voltage will be reached
16
within 0.1 second. If the power supply voltage is not reached quickly enough, the Timer may
malfunction or outputs may be unstable. Use a switch, relay, or other contact so that the
rated power supply voltage will be reached within 0.1 second. If the power supply voltage is
not reached quickly enough, the Timer may malfunction or outputs may be unstable.
) Use a switch, relay, or other contact to turn the power supply OFF instantaneously.
17
Outputs may malfunction and memory errors may occur if the power supply voltage is
decreased gradually.
18) If the set value is changed as follows during a timing operation, the output will turn ON because
of the use of a constant read-in system:
Elapsed time (UP) mode: Present value ≥ Set value
Remaining time (DOWN) mode: Elapsed time ≥ Set value (The present value is set to 0.)
In the remaining time mode, the amount the set value is changed is added to or subtracted from
the present value.
The operation under the set value 0 depends on the set output mode.
) Do not use organic solvents (such as paint thinners or benzine), strong alkali, or strong acids.
19
) Confirm that indications are working normally, including the backlight LEDs, and LCD. The
20
indicator LEDs, LCD, and resin parts may deteriorate more quickly depending on the
application environment, preventing normal indications. Periodic inspection and
replacement are required.
) The waterproof packing may deteriorate, shrink, or harden depending on the application
21
environment. Periodic inspection and replacement are required.
Ratings (Specifications)
100 to 240 VAC, 50/60 Hz
Voltage input
12 to 48 VDC/24 VAC, 50/60 Hz
24 to 240 VDC/24 to 240 VAC, 50/60 Hz
VDC: 90% to 110%)
Approx. 6.5 VA at 100 to 240 VAC
Control output
Approx. 5.4 VA/3.2 W at 24 VAC/12 to 48 VDC
Contact output
Approx. 5.6 VA/2.7 W at 24 to 240 VAC/24 to 240
Solid state output
VDC
°
°
-10 to 55
C (-10 to 50
C if Timers are mounted
side by side) (with no icing or condensation)
°
-25 to 70
C (with no icing or condensation)
Electrical life of relay
25% to 85%
2,000 m max.
Mechanical life of relay
Relay output: 0216005, Transistor output:0216.100
Approx. 115 g (main unit only)
External power supply
Ⅲ
Over-voltage category
, pollution degree 2,
Degree of protection
indoor use only (IEC 61812-1)
* Individual mounting: Degree of protection on the front panel of the Timer
Ω
conforms when all of the following conditions are satisfied:
ON impedance: 1 k
max. (Leakage current: 12
Ω
• The Y92S-P6 waterproof packing and Y92F-30 mounting adapter are used with
mA when 0
),
the Timer. Use only these parts for replacement.
ON residual voltage: 3 V max., OFF impedance:
Ω
100 k
min.
Nomenclature
9. DOWN Keys (DW1 to DW6)
H5CC
TIMER
10. Reset operation (UP6+DW6)
.
Press RST keys (UP6+DW6) simultaneously for at least one second.
4
1
.
LED on each key starts blinking. If not blink, that because the keys are not pressed
2
simultaneously. In this case, release the keys after pressing for at least 1 second,
5
and restart from 1. Do not release the keys until the LED starts blinking. Otherwise
6
the setting value may change.
.
Press and hold until the LED turns off. If you release the keys while blinking, the
3
reset operation will be interrupted.
8
12
11. Mode operation (UP1+UP3 or DW1+DW3)
9
<Change of setting item>
.
11
Press MODE keys (UP1+UP3 or DW1+DW3) simultaneously to switch setting items.
1
<Move to Function Setting Mode>
.
(yellow)
1
Press MODE key (UP1+UP3 or DW1+DW3) for at least 2 seconds simultaneously.
.
(yellow)
2
LEDs on UP1 (DW1) and UP3 (DW3) key start blinking. If not blink, that because the
keys are not pressed simultaneously. In this case, release the keys after pressing
(yellow) (Lit when the reset input or
for at least one second, and restart from 1. Do not release the keys until the LEDs
start blinking.
Otherwise the setting value may change.
Character
.
3
Press and hold until the LED turns off. If you release the keys during blinking, the
mode will not be moved to Function Setting Mode.
(green) (If the time range is 0
12. Status indicator
<When Run mode is selected.>
• When the indicator display mode is on, the LED indicator shows the percentage of
Character height: 6
the present value from 0 to 100%.
• When the indicator display mode is all off or all lit, the LEDs are all off or all lit.
(green)
Note: When you press the UP key or the DOWN key, the indicator display or all-lit
display goes off, and the LED indicator of the pressed key lights up or blinks.
<When Function Setting Mode is selected>
• The LED indicators at the settable key positions will light.
Table 1 Configuration Selection
Mode Settings
Display
Function
Select the function from Table 1
Timer
tim
using the UP1 or DW1 Key.
Twin timer
twn
Operation as a Twin timer
Step2
Note: Refer to the datasheet for detailed parameter settings.
Change from RUN Mode to Function Setting Mode.
UP1+UP3 or DW1+DW3
(2 s min.)
Power
Run
Function
ON
mode
setting mode
UP1+UP3 or DW1+DW3
(2 s min.)
Set the parameters using the UP Key or
DOWN Key.
The characters displayed in reverse video are the default
.
settings.
Press UP1+UP3 keys once to move to the previous parameter.
Press DW1+DW3 keys once to move to the next parameter.
Display
Parameter name
Set value
※1
OFF time range
oftr
※1
ON time range
ontr
UP/DOWN mode
,
timm
up
down
Twin Timer Output mode
totm
,
,
toff
ton
tof1
Input signal width
,
iflt
20ms
1ms
NPN/PNP input mode
,
imod
npn
pnp
Instantaneous/time-limit
,
otmd
1c1c
2c
1 ~
Set value upper limit 1
sl1h
999999
1 ~
sl2h
Set value upper limit 2
999999
,
,
kp-1
kp-2
kp-3
kypt
Key protect level
,
,
kp-5
kp-6
kp-7
□
□
×
H5CC-AU
and H5CC-L8E
1,000
×
Output 1 inversion
,
ot1i
1,000
n-o
n-c
Output 2 inversion
,
ot2i
n-o
n-c
Indicator display mode
,
,
indc
on
alof
allt
0 ~
~ 9999
Output 1 (OUT1)
on1a
100
ON count alarm set value
Output 2 (OUT2)
0 ~
~ 9999
on2a
ON count alarm set value
100
-
Output 1 (OUT1)
on1c
ON count monitor value
-
Output 2 (OUT2)
×
on2c
1,000
ON count monitor value
0.0 ~
~ 99.9
ot-a
Total run time alarm set value
10.0
-
Total run time monitor
ot-c
value
-
Software version
ver
□
Models Other Than H5CC-AU
and H5CC-L8E
Output inversion
,
ot-i
n-o
n-c
indc
Indicator display mode
,
,
on
alof
allt
0 ~
~ 9999
on-a
Output ON count alarm set value
100
-
on-c
Output ON count monitor value
0.0 ~
~ 99.9
ot-a
Total run time alarm set value
10.0
-
Total run time monitor
ot-c
value
-
Software version
ver
*1 The set values for the time range are the same as for Timer operation.
Self-diagnostic Functions
The following displays will appear if an error occurs.
Main
Sub-
Output
Description
Correctionmethod
display
display
status
Either perform Reset
operation or reset
Not lit CPU error
OFF
e1
the power supply.
Turn ON the power
Not lit Memory error (RAM)
OFF
e2
again.
Memory error
OFF
Reset operation
e2
sum
(non-volatile memory) *1
Total run time or Output
No
No
Rplc
Reset operation *2
ON count has reached
*3
change
change
the maintenance forecast.
1) Read this manual carefully before using the product.
2) An inrush current of approx. 14 A will flow for a short time when the power supply
is turned ON. If the capacity of the power supply is not sufficient, the Timer may
not start. Be sure to use a power supply with sufficient capacity.
3) Make sure the power supply voltage and loads are within the specifications and
ratings for the product.
4) Take caution that signal reception is possible, impossible, or indefinite during the
following periods after power ON/OFF. To allow for the startup time of peripheral
devices (sensors, etc.), the Timer starts timing operation between 200 to 250 ms
after power is turned ON. For this reason, if the set value is 249 ms or less in
operations where timing starts from power ON, the time until output turns ON will
be a fixed value between 200 and 250. The present value display will start from
250 ms. (Normal operation is possible for set values of 250 ms or more.) In
applications where a set value of 249 ms or less is required, use start timing with
signal input.
5) No input signals will be accepted from 5 to 505 ms for H5CC-A
105 ms for H5CC-A11F, and from 5 to 1005 ms for H5CC-AU
turned OFF.
6) Inrush current generated by turning ON or OFF the power supply may deteriorate
contacts on the power supply circuit. Turn ON or OFF to a device with the rated
current of more than 14 A.
7) Make sure that all settings are appropriate for the application. Unexpected
operation resulting in property damage or accidents may occur if the settings are
not appropriate.
8) Do not leave the Timer for long periods at a high temperature with output current
in the ON state. Doing so may result in the premature deterioration of internal
components (e.g., electrolytic capacitors). Do not install the product close
contact with the heating element.
9) Non-volatile memory is used as backup memory when the power is interrupted.
The write life of the non-volatile memory is 100,000 writes. The non-volatile
memory is written when the power is turned OFF or when switching from function
setting mode or configuration selection mode to run mode.
10) Dispose of the product according to local ordinances as they apply.
11) Do not use because it may be damaged inside the product when the product fall
by mistake.
12) Confirm the wiring the input and output terminals correctly before power is
supplied.
13) Do not use the product near radio wave receivers. Doing so may cause incoming
radio wave interference.
14) Install product so that the load doesn't span the product body.
15) H5CC models with a 24 to 240 VAC/DC power supply use a transformer-free
power supply method in which the power supply terminals are not isolated from
the signal input terminals. In such cases, unwanted current paths may
occasionally burn or destroy internal components depending on the wiring.
Always check the wiring sufficiently before use.
16) Do not wire the terminals that are not used.
17) If there is a transformer or other device with a large inductance component on the
power supply line, the inductance will cause a reverse voltage. If that occurs,
insert a CR filter in the power supply line to reduce
the reverse voltage.
18) Do not use in a circuit with the waveform is
distorted. The error will increase due to the
High (logic) level: 4.5 to 30 VDC, Low (logic) level:
influence of the distorted waveform.
Ω
0 to 2 VDC (Input resistance: approx. 4.7 k
)
19) The capacity of the external power supply is 100 mA
No-voltage (NPN) input/voltage (PNP) input
□
at 12 V. When using H5CC-AUD with the DC power
(switchable) (H5CC-A11F/H5CC-L8
supports
supply, however, reduce the load with the power
no-voltage input only)
supply voltage, as shown in the diagram on the
right.
250 VAC/30 VDC 5A (resistive load)
Open collector 30 VDC max., 100 mA max.
Residual voltage 1.5 VDC max. (Effective value:
Approx. 1 VDC)
Leakage current 0.1 mA max.
100,000 operations (at an ambient temperature
°
of 23
C)
• When conforming to EMC standards, refer to the information provided in this
10,000,000 operations (at an ambient
°
Instruction Manual for cable selection and other conditions.
temperature of 23
C)
□
12 VDC 100 mA (H5CC-AU
only)
• This is a class A product. In residential areas it may cause radio interference, in which
IEC IP66
case the user may be required to take adequate measures to reduce interference.
• Basic insulation is provided between power supply and input terminals. (There is no
insulation between power supply and input terminals for H5CC-A11.) Basic insulation
is provided between power supply and output terminals and between input and
output terminals.
• Basic insulation is provided between power supply and output terminals, and between
input and output terminals. When double insulation or reinforced insulation is
required, apply double insulation or reinforced insulation as defined in IEC 60664 that
is suitable for the maximum operating voltage with clearances or solid insulation.
• Connect the input and output terminals to devices that do not have any exposed
charged parts.
(DW 1, 2, 3, 4, 5 and 6 from right to left)
Notice to Users of the H5CC in the USA and Canada
Please use the following installation information instead of the general information in
the instruction manuals in order to use the product under certified conditions of UL and
CSA when the product is installed in the USA or Canada. These conditions are required
by NFPA 70, National Electrical Code in the USA and the Canadian Electrical Code, Part
I in Canada and may vary from information given in the product manuals or safety
precautions.
• Installation in a Panel
H5CC is normally installed on a flat surface in an operation panel. Use a Type 1
Enclosure for the operation panel.
• Environment
Surrounding Air Temperature: -10 to 40
• Accessories (Order Separately)
• Wire properly after checking the specifications of the power supply voltage.
• Do not wire the terminals that are not used.
H5CC-A/AD
H5CC-AU/AUD
-
(
)
Sensor
+
(
)
12 VDC
Display in RUN mode.
External
power supply
12.34
Present value
10.00
OFF Set value
* UP1+UP3 or
DW1+DW3
H5CC-A11S/A11SD
12.34
Present value
18.50
ON Set value
* Each time the UP1+UP3 or DW1+DW3 Key are
pressed, the set value display (6) will switch
between OFF Set value and ON Set value.
Comments
-
-
H5CC-L8S/L8SD
-
,
Only modes
and
can be selected for H5CC-L8E
.
ton1
toff
ton
□
Displayed only for models other than H5CC-L8E
and H5CC-A11F.
□
Displayed only for models other than H5CC-L8
and H5CC-A11F.
Displayed only for the H5CC-L8E
.
-
-
* :
NPN output
,
,
-
kp-4
-
-
-
Input Connections
×
1,000
No-voltage Inputs (NPN Inputs)
×
1,000
Open Collector
The monitor value is only displayed. It cannot be set.
×
PLC,
1,000
Sensor
The monitor value is only displayed. It cannot be set.
×
1,000
Unit: year
The Total run time monitor value is only
Note: Operate with transistor ON
displayed. It cannot be set.
Voltage Inputs (PNP Inputs)
The software version is only displayed.
It cannot be set.
No-contact Input (NPN Transistor) No-contact Input (PNP Transistor) Contact Input
□
-
Sensor
-
×
1,000
×
The monitor value is only displayed. It cannot be set.
1,000
Note: Operate with transistor OFF
Unit: year
The Total run time monitor value is only
displayed. It cannot be set.
OMRON Corporation
The software version is only displayed.
It cannot be set.
Kyoto, JAPAN
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69,2132 JD Hoofddorp
*1. This includes times when the life of the
The Netherlands
non-volatile memory has expired.
Set value
Tel: (31)2356-81-300
*2. This is displayed if the alarm set value for either
after reset
of the two outputs is exceeded if a model with
Fax: (31)2356-81-388
two outputs is used. The total ON count will not
be cleared by using Reset operation.
*3. The normal display and
will appear
No change
OMRON ASIA PACIFIC PTE. LTD.
Rplc
alternately. When Reset operation is performed,
No. 438A Alexandra Road #05-05/08
will no longer be displayed even if the alarm
Rplc
set value is exceeded. (Monitoring is possible,
(Lobby 2), Alexandra Technopark,
No change
however, because the Timer will continue without
Singapore 119967
clearing the total run time and the output ON
count.) If the power supply is turned OFF/ON
Factory
Tel: (65) 6835-3011
after the
display is turned OFF by Reset
setting
Rplc
Fax: (65) 6835-2711
operation,
will be displayed again. In order
Rplc
to prevent the display even after the power supply
No change
is turned OFF/ON, change the alarm set value to
equal to or greater than the count value, or
change the alarm set value to 0 to be invalid.
Note: Specifications subject to change without notice.
Precautions for Correct Use
/L8
, from 5 to
after the power is
100
Load
current
(mA)
20
0
10.8
15
Power supply voltage (VDC)
Conformance to EN/IEC Standards
Precautions for Compliance with
UL Standards and CSA Standards
Track Mounting/
11-pin
P2CF-11
°
Front Connecting
11-pin, finger-safe type
P2CF-11-E
C
Socket
8-pin
P2CF-08
8-pin, finger-safe type
P2CF-08-E
Terminal Arrangement
H5CC-AS/ASD
0 V
0 V
6
7
8
9
6
7
8
9
1
2
3
4
5
1
2
3
4
5
Contact output
Solid state output*
-
+
-
+
(
)
(
)
(
)
(
)
H5CC-A11/A11D/A11F
Reset
Signal
Gate
0 V
Internal circuit
6 7
5
6
7
8
9
Unused
4
8
0 V
3
9
Contact
2
10
output
Solid state
1
11
11
12
13
output*
Unused
1
2
3
4
5
-
+
(
)
(
)
Contact output
Terminals 2 and 3 of the H5CC-A11F
-
+
(
)
(
)
are connected internally.
H5CC-L8/L8D
Reset
Signal
Internal circuit
Signal
Gate
Internal circuit
6 7
4
5
5
Reset
Unused
4
8
3
6
0 V
Contact
3
9
output
Solid state
2
7
2
10
output*
1
8
1
11
0 V
Unused
-
+
-
+
(
)
(
)
(
)
(
)
H5CC-L8E/L8ED/L8EF
Internal circuit
Internal circuit
Internal circuit
Signal
Unused
4
5
4
5
Reset
3
6
Instantaneous
3
6
Time-limit
Solid state
contact output
contact output
output*
2
7
OUT1
2
7
OUT2
1
8
1
8
0 V
-
+
-
+
(
)
(
)
(
)
(
)
PNP output
With Inductive Load
The diode connected to
Timer
the collector of the
output transistor is used
to absorb inverted
voltage that is generated
Load
Load
Inductive
+
+
when an inductive load is
+
load
connected to the H5CC.
Power for load
Power for load
Power for load
Voltage Output
Contact Input
Sensor
V
V
V
0
0
0
Note: Operate with transistor ON
Note: Operate with relay ON
Sensor
V
V
V
0
0
0
Note: Operate with transistor ON
Note: Operate with relay ON
Industrial Automation Company
Contact: www.ia.omron.com
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900
Fax: (1) 847-843-7787
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
Pu Dong New Area, Shanghai,
200120, China
Tel: (86) 21-5037-2222
Fax: (86) 21-5037-2200