Enclosure Ventilation Requirements

The VF Fire Pit burner enclosure must be ventilated to properly cool the fire pit (see illustration below for details).
The enclosure must be ventilated in accordance with the requirements listed below to allow the
appliance to cool. Failure to provide this ventilation will create a severe fire risk. The ventilation
grills must be installed within 24" of the appliance.
Enclosure Ventilation Overview
The VF Fire Pit Burner enclosure must have at least (2)
vents. The vents must be on opposite sides of the
enclosure from each other (either on the ends (a) or
along the sides (b). Each vent must provide a minimum
of 9 square inches of free area.
 
Example: If (w) = 4" and (h) = 2"
4" x 2" = 8 square inches
8"
< 9" (the minimum)
NOT LARGE ENOUGH
Example: If (w) = 12" and (h) = 2"
2" x 12" = 24 square inches
24"
> 9" (the minimum)
LARGE ENOUGH

Enclosure Ventilation Grills

Use grills to ventilate the enclosure. The grills must provide 18 square inches of free area opening (9 square
inches each) into the enclosure cavity. The grills must be located within 24" of the appliance.
The grills must be attached directly to the enclosure cavity.
The grills must have a 1/4" screen to prevent debris, animals, etc., from entering the enclosure.
The grills should not be placed in a location where they could become blocked.
The ventilation air for the enclosure MUST be drawn from outdoor air only.
The grills should be installed into the enclosure as low as possible.
Facing may be applied over the flange of the grills but cannot protrude over the screened opening.
The grills may be painted.
The grills must be located within 24" of the appliance.
© Travis Industries, Inc.
Installation
9/27/2023 - 1589
(qualified installers only)
WARNING
VF Outdoor Fire Pit Burners