Extended Settings - oventrop ClimaCon F 316 Operating Instructions Manual

Table of Contents

Advertisement

ClimaCon F 316
Commissioning
7.1.5

Extended settings

NOTICE
Malfunctions due to improper configuration!
Improperly configured extended settings can cause
unexpected room temperatures and damage parts
of the system.
!
Extended settings may only be carried out by
specialist tradespeople who are sufficiently
qualified.
7.1.5.1 Unit
Here you can choose between the units °Celsius
and °Fahrenheit.
This setting affects all temperature settings in the
app and at the room thermostat.
7.1.5.2 Operating mode
Here you can switch between the operating
modes Heating / Cooling / Heating and Cooling .
7.1.5.3 Applications
Application 1:
Optibal W6 six-way ball valve with modulating
actuator
Application 2:
Optibal W6 six-way ball valve with on/off
actuator plus control valve with modulating
actuator, e.g. Cocon QTZ
7.1.5.4 Limit voltage 0-10V (only application 1)
In application 1, the rotary actuator is controlled
with a continuous voltage of 0 to 10 Volt.
The values set here at the factory are matched to
the Optibal W6 six-way ball valve. If you use a
different six-way ball valve, you must adjust the
values accordingly.
Cooling
Modulating control of the six-way ball valve in
cooling mode
Dead zone
In this zone, the six-way ball valve is in the
middle position (neither cooling nor heating)
Heating
Modulating control of the six-way ball valve in
heating mode
7.1.5.5 Configuration 0-10 V (only application 2)
Depending on the actuator used, e.g. for Cocon
QTZ valve, the appropriate voltage values can be
entered here.
18
7.1.5.6 Hysteresis
By setting a hysteresis, you define the value by
which the measured temperature may deviate
from the setpoint temperature before the
actuator is opened for heating or cooling.
The optimum value depends on the design of the
system.
7.1.5.7 Safety sensors
If this function is activated, you can use sensors
for temperature (safety temperature limiter) or
dew point (dew point monitor) on terminals 6 and
7. If the electrical connection between terminals 6
and 7 is interrupted by triggering a sensor, the
room thermostat interrupts heating or cooling
mode.
7.1.5.8 Output signal 0 - 10 V
The reaction of the 0-10 V output is influenced by the P
and I components.
P component
Setting of the height of the proportional band of the PI
controller.
The value for the P component must always be
higher than the value for the hysteresis.
I component
Setting of the height of the integral component of the PI
controller.
7.1.5.9 Valve protection
Once a week, the actuator is fully opened and
closed. This ensures that the valve cannot get
stuck during a longer standstill.
The point in time within the week can be set here.
10231719 000 00