Design; Functional Description; Applications; App Connection - oventrop ClimaCon F 316 Operating Instructions Manual

Table of Contents

Advertisement

ClimaCon F 316
Technical description
3.2

Design

1
Fig. 3:
Design
1
Control unit
2
Mounting plate
3
Terminal strip
4
Opening for the cable feed
5
Release clip
3.3

Functional description

The ClimaCon F 316 room thermostat controls electronic
actuators via a cable connection. Areas of application are
e.g. heating and cooling ceilings, radiant ceiling panels or
ceiling sails.
Optibal W6 six-way ball valves and, if necessary, control
valves are opened or closed via the actuators.
The setpoint temperature is set on the room thermostat
or in the app connected to the room thermostat.
3.3.1

Applications

3.3.1.1 Application 1
Modulating control of the Optibal W6 six-way ball valve is
carried out via a 0 – 10 V signal. The flow is limited via the
Kvs orifices of the six-way ball valve.
3.3.1.2 Application 2
The Optibal W6 six-way ball valve switches between
heating and cooling mode via an on/off control. The flow
is controlled via the Cocon QTZ control valve, which is
modulating-controlled via a 0 – 10 V signal.
8
2
3
5
4

3.3.2 App connection

The ClimaCon F 316 room thermostats can be
programmed via smartphone app.
Three modes are available for temperature control.
3.3.2.1 Auto mode
In Auto mode, the temperature control follows a time
profile (see section 7.1.3.2 on page 15).
3.3.2.2 Eco mode
In Eco mode, the temperature is constantly regulated to
the "Eco temperature" (see section 7.1.3.1 on page 15).
ClimaCon F 316 devices are equipped with an Eco output
(leader). Whenever the Eco mode is active, a voltage is
present at this output. The Eco output can be connected
to the Eco input (follower) of a ClimaCon F 90, F 100 room
thermostat. The voltage at the Eco input reduces the
temperature at the follower room thermostat by 4 Kelvin
compared to the temperature set at the scale (heating
mode).
3.3.2.3 Manual mode
You always have the option to set the temperature
manually (see section 8.1.3 on page 19).
3.3.3

Functions in detail

Dot-Matrix display for visualisation of the setpoint
temperature, the actual temperature, various error
codes, the display "BLu" for the teach-in mode, as well
as the OFF display when the device is switched off
LED display heating or cooling
LED display with touch surfaces for adjusting the
setpoint temperature via the Plus and Minus keys and
for switching between Auto and Eco mode
Automatic switching between heating and cooling
Control via app (Bluetooth)
Possible modes: Auto (daily or weekly schedule), Eco/
Setback, Manual
Frost protection (6 °C/ 43 °F) is activated when the
room thermostat is switched off
Temperature limitation and offset temperature
adjustable
Leader output for controlling the setback temperature
of a follower room thermostat
A dew point monitor and a safety temperature limiter
can be connected (series connection).
The dew point monitor interrupts the circuit of the
safety sensors if dew has formed due to the flow
temperature of the cooling circuit being too low.
The safety temperature limiter interrupts the circuit of
the safety sensors if the flow temperature of the
heating circuits exceeds the set limit value.
10231719 000 00