ClimaCon F 316
Mounting
6.3

Mounting of the mounting plate

The ClimaCon F room thermostat is designed for
surface-mounted installation.
Operate the room thermostat at a location in the
room where the room air is well distributed.
Mount the room thermostat on an interior wall or
on a pillar, at a height of 140 cm to 170 cm. Make
sure that the room thermostat is not thermally
influenced by extraneous heat (e.g. solar radiation
or nearby heating devices).
The supply line is fed into the device through the
opening for the cable feed (position
page 8). The supply line must therefore
already protrude from the wall at the designated
location. The cross-section of the cores must be
2
0.5 – 2.5 mm
for flexible lines and 1 – 2.5 mm
for fixed wiring. The line type used must have a
rated voltage of at least 300 V (e.g. NYM cable).
Alternatively, the mounting plate can also be
mounted on a standard flush-mounted box.
For mounting and installing the actuators you
use, observe the respective operating
instructions.
Fig. 6:
Mounting of the mounting plate
1
Hold the mounting plate flat against the wall and align
it perpendicularly.
2
Mark the drill holes with a pen.
WARNING
Danger to life due to electric current !
Damage to live lines can cause electric shocks or
fires.
!
Be careful not to drill into electrical lines.
10231719 000 00
3
4
6.4
4
in Fig. 3 on
6.4.1
2
Fig. 7:
Terminal
1
2
3
4
5
6
7
8
9
10
Drill at least two holes (opposite each other) and insert
dowels.
Screw on the mounting plate.
Only use device screws for switch boxes
(countersunk screws).
If you use screws with thicker screw heads, you
will not be able to mount the control unit.
Electrical connection of the room
thermostat

Terminal assignment

ClimaCon F - Electrical connection
Assignment
IN (L1 24 V AC) operating voltage
IN (L2 24 V AC) operating voltage
OUT (L1 24 V AC) on/off
OUT (L1 24 V AC) Eco output
Input, not assigned
IN (A) ext. safety sensors
IN (B) ext. safety sensors
OUT (Signal) 0-10 V (max. 10 mA)
OUT (NO) potential-free contact
(max 24 V, 90 mA DC/AC)
OUT (COM) potential-free contact
(max 24 V, 90 mA DC/AC)