Climacon F 210, F 310 - Extended Settings - oventrop ClimaCon F Series Operating Instructions Manual

Table of Contents

Advertisement

ClimaCon F
Commissioning
7.2.4.8 Firmware room thermostat
Fig. 18:
ClimaCon F app - Firmware update
1
Call-up of the firmware update
7.2.4.9 Extended settings
Fig. 19:
ClimaCon F app - Call-up of the extended
settings
1
Call-up of the extended settings
Fig. 20:
ClimaCon F App - Entering the installer code
f
To call up the extended settings, enter the installer code
2962 and confirm the entry with "OK".
20
7.2.5
NOTICE
Malfunctions due to improper configuration
1
Improperly configured extended settings can cause
unexpected room temperatures and damage parts
of the system.
!
Extended settings may only be carried out by
specialist tradespeople who are sufficiently
qualified.
7.2.5.1 Unit
1
7.2.5.2 Operating mode
7.2.5.3 Sensor (F 310 24 V)
7.2.5.4 External limitation (F 310 24 V)
ClimaCon F 210, F 310 - Extended
settings
Here you can choose between the units °Celsius
and °Fahrenheit.
This setting affects all temperature settings in the
app and at the room thermostat.
Here you can switch between the operating
modes.
ClimaCon F 210: Heating / Cooling
ClimaCon F 310: Heating / Cooling / Heating or
cooling
The room temperature can be measured via the
internal sensor or optionally via an external
sensor.
Here you select which sensor is to be used.
If a temperature sensor is connected to measure
the surface temperature, the maximum/minimum
permissible temperatures can be set here.
If these temperatures are exceeded or undercut,
the connected actuator is closed.
This can only be selected if the internal sensor is
used for temperature measurement.
115500983-V02.01.2022