5 Electrical installation
Detail C4: Connection of X11Y
Factory-mounted cables.
Disconnect X11Y from X11YA, and connect it to X11YB.
X2M/5+6
X11Y
Detail C5: Option kit EKGSPOWCAB
Install the option kit EKGSPOWCAB (= power cable for split
power supply). For installation instructions, see the installation
manual of the option kit.
Z15C
N=1
EKGSPOWCAB
1
3
I
I
F2B
2
4
Q2DI
L
N
1N~, 50 Hz, 230 V AC
F2B
Overcurrent fuse (field supply). Recommended fuse:
2‑pole, 16 A fuse, C curve.
Q2DI
Earth leakage circuit breaker (field supply)
Configuration power supply
[9.3] Backup heater
[9.8] Benefit kWh power supply
Installation manual
18
X11YB
Z1F
X11YA
X22YB
X22Y
1
Z2F/1
2
Z2F/2
3
Z2F/3
5.4
To connect the remote outdoor
sensor
The remote outdoor sensor (delivered as accessory) measures the
outdoor ambient temperature.
INFORMATION
If the desired leaving water temperature is weather
dependent, the full time outdoor temperature measurement
is important.
Remote outdoor sensor + cable (40 m) delivered as accessory
[9.B.2] Ext. amb. sensor offset (= overview field setting
[2‑0B])
[9.B.3] Averaging time (= overview field setting [1‑0A])
1 Connect the external temperature sensor cable to the indoor
unit.
a
b
c
a
Factory-mounted cable
b
Splicing connectors (field supply)
c
Remote outdoor sensor cable (40 m)(delivered as
accessory)
d
Remote outdoor sensor (delivered as accessory)
2 Fix the cable with cable ties to the cable tie mountings.
3 Install the remote outdoor sensor outside as described in the
installation manual of the sensor (delivered as accessory).
5.5
To connect the shut-off valve
(Heating/Cooling)
INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
Wires: 2×0.75 mm²
Maximum running current: 100 mA
230 V AC supplied by PCB
[2.D] Shut off valve
1 Open the following (see
"3.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Installer switch box cover
d
unit" [ 4  7]):
1
3
2
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12