Configuration Wizard: Main Zone; Configuration Wizard: Additional Zone - Daikin Altherma 3 GEO EGSAH06UD Series Installation Manual

Table of Contents

Advertisement

Voltage
Depending on how the backup heater is connected to the grid and
what voltage is supplied, the correct value needs to be set. In either
configuration, the backup heater will operate in steps of 1 kW.
#
Code
[9.3.2]
[5‑0D]
▪ 0: 230V, 1ph
▪ 2: 400V, 3ph
Maximum capacity
During normal operation the maximum capacity is:
▪ 3 kW for a 230 V, 1N~ unit
▪ 6 kW for a 400 V, 3N~ unit
The maximum capacity of the backup heater can be limited. The set
value depends on the used voltage (see table below) and is then the
maximum capacity during emergency operation.
#
Code
(a)
[9.3.5]
[4-07]
0~6 kW when voltage is set to 230 V,
1N~
0~9 kW when voltage is set to 400 V,
3N~
(a)
If the value [4-07] is set lower, then the lowest value will be used
in all operation modes.
7.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.
Emitter type
Heating up or cooling down the main zone can take longer. This
depends on:
▪ The water volume of the system
▪ The heater emitter type of the main zone
The setting Emitter type can compensate for a slow or a quick
heating/cooling system during the heat up/cool down cycle. In room
thermostat control, Emitter
modulation of the desired leaving water temperature, and the
possibility for usage of the automatic cooling/heating changeover
based on the indoor ambient temperature.
It is important to set Emitter type correctly and in accordance with
your system layout. The target delta T for the main zone depends on
it.
#
Code
▪ 0: Underfloor heating
[2.7]
[2‑0C]
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
Description
0: Underfloor heating
1: Fancoil unit
2: Radiator
Control
Define how the operation of the unit is controlled.
EGSAH/X06+10UD
Daikin Altherma 3 GEO
4P598591-1C – 2023.02
Description
Description
type influences the maximum
Description
Space heating setpoint range
Maximum 55°C
Maximum 65°C
Maximum 65°C
Control
Leaving water
Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.
External room
Unit operation is decided by the external
thermostat
thermostat or equivalent (e.g. heat pump
convector).
Room thermostat Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).
#
Code
[2.9]
[C‑07]
▪ 0: Leaving water
▪ 1: External room thermostat
▪ 2: Room thermostat
Setpoint mode
Define the setpoint mode:
▪ Fixed: the desired leaving water temperature does not depend on
the outdoor ambient temperature.
▪ In WD heating, fixed cooling mode, the desired leaving water
temperature:
▪ depends on the outdoor ambient temperature for heating
▪ does NOT depend on the outdoor ambient temperature for
cooling
▪ In Weather
dependent mode, the desired leaving water
temperature depends on the outdoor ambient temperature.
#
Code
[2.4]
N/A
Setpoint mode:
▪ Fixed
▪ WD heating, fixed cooling
▪ Weather dependent
When weather dependent operation is active, low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user can shift the water
temperature up or down by a maximum of 10°C.
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:
▪ In Fixed LWT setpoint mode, the scheduled actions consist of
desired leaving water temperatures, either preset or custom.
▪ In Weather
dependent LWT setpoint mode, the scheduled
actions consist of desired shift actions, either preset or custom.
#
Code
▪ 0: No
[2.1]
N/A
▪ 1: Yes
7.2.6

Configuration wizard: Additional zone

The most important settings for the additional leaving water zone
can be set here.
Emitter type
For more info about this functionality, see
zone" [ 4  31].
wizard: Main
7 Configuration
In this control...
Description
Description
Description
"7.2.5  Configuration
Installation manual
31