Banner DX80G9M2S-P7 Manual page 5

Surecross performance flexpower gateway
Hide thumbs Also See for DX80G9M2S-P7:
Table of Contents

Advertisement

SureCross Performance FlexPower Gateway
2
3
1
5
4
Terminal Blocks and Wiring (12 Sinking I/O Models)
PWR
PWR
GND
GND
IO7
IO6
IO8
IO5
IO9
IO4
IO3
IO10
IO11
IO2
IO12
IO1
12 I/O Sinking Models
Discrete Input Wiring for NPN Sen-
sors
DIx
GND
dc common
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model.
Terminal Label Gateway, DX85
V+
10 to 30V dc
Tx/+
RS485 / D1 / B / +
V-
dc common (GND)
Rx/-
RS485 / D0 / A / -
B+
Connecting dc power to the communication pins (Tx/Rx) will cause permanent damage. For FlexPower devices, do not apply more than
5.5V to the gray wire.
Terminal Blocks (IP20 Base)
This is the wiring board for the DX80**X2S-P7C IP20 models.
For the default configuration of 6 IN and 6 OUT, use IO 1 through 6 to wire the inputs and IO 7 through 12 to wire the outputs.
When using the DIP switches to configure the input and output selection, wire the inputs beginning with IO1. After all inputs are wired,
begin using the remaining IOx as outputs. For example, if you are using 10 inputs and 2 outputs, use terminals IO1 through 10 for the
inputs and terminals IO 11 and 12 for the outputs.
P/N 155285_web
Rev. D
Wire No.
Wire Color
1
Brown
2
White
3
Blue
4
Black
5
Gray
IOx. Input or output (depending on configuration)
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
For the default configuration of 6 IN and 6 OUT, use IO 1 through 6 to wire
the inputs and IO 7 through 12 to wire the outputs.
When using the DIP switches to configure the input and output selection,
wire the inputs beginning with IO1. After all inputs are wired, begin using
the remaining IOx as outputs. For example, if you are using 10 inputs and 2
outputs, use terminals IO1 through 10 for the inputs and terminals IO 11
and 12 for the outputs.
Discrete Output Wiring (NPN or NMOS)
PWR
10-30V dc
DOx
Load
GND
dc common
10 to 30V dc Powered Nodes
10 to 30V dc
dc common (GND)
www.bannerengineering.com - tel: 763-544-3164
10 to 30V dc
RS485 / D1 / B / +
dc common (GND)
RS485 / D0 / A / –
3.6 to 5.5V dc
The DIx and DOx of these wiring diagrams
correspond to the IOx on the terminal
block.
Battery Powered Nodes
dc common (GND)
3.6 to 5.5V dc
5