Wiring Of Terminals Related To The Encoder - Mitsubishi Electric 800 Series Instruction Manual

Vector control terminal block
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

3.3.3

Wiring of terminals related to the encoder

Use shielded twisted pair cables (0.2 mm
use several cables in parallel or use a thick cable, according to the wiring length. To protect the cables from noise, run them
away from any source of noise (e.g. the main circuit and power voltage).
Parallel connection
Wiring length
(Cable gauge 0.2 mm
Within 10 m
At least two cables in parallel
Within 20 m
At least four cables in parallel
*1
At least six cables in parallel
Within 100 m
*1
When differential line driver is set and a wiring length is 30 m or more.
The wiring length can be extended to 100 m by increasing the 5 V power supply (approximately to 5.5 V) while using six or more 0.2 mm
gauge cables in parallel or a 1.25 mm
2
or larger) for connection the encoder. For the wiring to the terminals PG and SD,
Example of parallel connection
with two cables
(with complementary encoder output)
FR-A800
(FR-A8TP)
PA3
PAR3
PB3
PBR3
PZ3
PZR3
PG
SD
PG24
2
2 mm
Larger-size cable
2
)
2
0.4 mm
or larger
2
0.75 mm
or larger
2
1.25 mm
or larger
2
or larger gauge cable. The voltage applied must be within power supply specifications of encoder.