Annex A System Water Additives - Atag iR 12 Installation & Servicing Instructions Manual

Open vent system
Table of Contents

Advertisement

Annex A System water additives

When the filling water requirements as referred to in chapter Water Quality have been met, certain additives are
allowed for the below mentioned applications and related dosage. Warranty on ATAG delivered installation products
expires, if these additives and concentrations are not used in accordance with this annex.
Additive type
Corrosion inhibitors
Anti-freeze
System cleaners
ATAG support the use of inhibitors suitable for mixed metal applications that keep the pH level between 6 and 8.
Dosage levels as per manufacturers instructions. Preferred inhibitor suppliers are ATAG Heating Technology,
Fernox and Sentinel.
Installation & Servicing instructions ATAG iR-Range
Supplier and specifications
ATAG Central Heating Protector.
Build Cert Approved
Sentinel X100 Corrosion resistant
protection agent of CH systems
Kiwa certified
Fernox F1 Protector Corrosion
resistant protection agent of CH
systems
Kiwa certified KIWA-ATA K62581,
Belgaqua certified Cat III
Kalsbeek
Monopropyleneglycol / propane-
1,2-diol
+ inhibitors
AKWA-Colpro KIWA-ATA Nr.
2104/1
Tyfocor L
Monopropyleneglycol / propane-
1,2-diol
+ inhibitors
Sentinel X500
Monopropyleneglycol + inhibitors
Kiwa certified
Fernox Alphi 11
Monopropyleneglycol + inhibitors
Kiwa certified KIWA-ATA K62581,
Belgaqua certified Cat III
ATAG Central Heating Universal
Cleaner
Sentinel X300
Solution of phosphate, organic
heterocyclic compounds, polymers
and organic bases
Kiwa certified
Sentinel X400
Solution of synthetic organic
polymers
Sentinel X800 Jetflo
Aqueous emulsion of dispersants,
moistening agents and inhibitors
Fernox F3 Cleaner
Liquid pH neutral universal
cleaner for pre-commissioning
new systems
Fernox F5 Cleaner, Express
pH neutral universal cleaner
concentrate for pre-commissioning
new systems
Max. concentration
500 ml / 100 litres
1-2 l/100 litres CH water content
500 ml can or 265 ml Express /
100 litres CH water content
50% w/w
50% w/w
20-50% w/w
25-50% w/w
500 ml / 100 litres
1 litre / 100 litres
1-2 litres / 100 litres
1-2 litres / 100 litres
500 ml / 100 litres
295 / 100 litres
Application
Suitable for mixed metal and
plastic systems. Prevents
corrosion and limscale.
Aqueous solution of organic
and inorganic agents preventing
corrosion and scale forming
Preventing corrosion and scale
forming
Anti-freeze
Anti-freeze
Anti-freeze
Anti-freeze in combination with F1
Protector
Suitable for mixed metal and
plastic systems. Disperses sludge,
limescale and other deposits.
For new CH installations Removes
oils/grease and flow control
agents
For cleaning existing CH-
installations Removes sediments.
For cleaning new and existing CH-
installations Removes iron and
lime-related sediments.
For cleaning new and existing
CH-installations Removes sludge,
limescale and other debris.
For cleaning new and existing
CH-installations Removes sludge,
limescale and other debris.
47