Checking The Co - Atag iR 12 Installation & Servicing Instructions Manual

Open vent system
Table of Contents

Advertisement

15.1

Checking the CO

The CO
percentage is set in the factory. This has to be checked during inspection, maintenance and
2
in case of a failure.
This can be verified by means of the following action:
- Set the external controls to call for heat;
- Make sure the boiler is operational and can get rid of the heat it produces;
- Calibrate the flue gas analyser;
- Place the lance of the flue gas analyser into the flue gas test point (see Figure 15.1.a);
- Press both + buttons for 6 seconds;
- When the flame symbol appears in the display press both + buttons again for 6 seconds;
- The display shows the supply water temperature (
The boiler will switch to maximum power of the heating capacity
- Press 1x the eco- button;
the display shows XX% (heating capacity)
- Leave measuring CO
- CO
percentage at full load =
2
- If required, you may turn the setting screw to set the correct CO
(refer to Figure 15.1.b).
Installation & Servicing instructions ATAG iR-Range
2
Measuring point CO
°C
to the measuring equipment.
2
Natural gas
9.0% (-0.4%, +0.6%)
Adjustment screw CO
Figure 15.1.a
2
appears in the display);
Propane
10.3% (+/- 0.6%)
percentage.
2
Figure 15.1.b
2
39