5.2

Example of Basic settings

Basic settings should only be seen as setting values to get burner to start.
Once the burner has started and established flame, it is necessary to adjust
the settings so that they are adapted to the installation and the fuel used.
B 40 A
Burner output:
Estimated nozzle output:
(* Calorfic value Fuel oil
This provides the following nozzle according to the nozzle table, (see Technical
data).
Nozzle:
Pump pressure:
Setting values for 265 kW according to basic setting diagram, (see Technical
data).
Air setting:
Insert setting:
20
Bentone
265 kW
265 / 11.86*
22.3 kg/h
=
11.86 kWh/kg)
=
6.00 Gph
10.0 bar
=
=
8.0
2.0
165 105 40-4