Basic Settings; Example Of Basic Settings - Bentone ST 120 R Installation And Maintenance Instruction

Table of Contents

Advertisement

4. Basic settings

4.1 Example of basic settings

4.1.1
Choice of nozzle
ST 120 R 69-16
Burner output
Estimated nozzle output:
Choice of nozzle according to the table, (see Technical data).
According to the nozzle table, this provides the following nozzle.
Nozzle:
Pump pressure:
ST 120 RV 69-16
Burner output
Output calculation due to preheater for nozzle choice according to the table,
(see Technical data).
Estimated nozzle output:
Choice of nozzle according to the table, (see Technical data).
According to the nozzle table, this results in the following nozzle.
Nozzle:
Pump pressure:
* Energy value of EO1 fuel oil = 11.86 kWh/kg
4.1.2 Basic settings
Setting values for 30 kW according to the basic setting table.
Air setting
Nozzle assembly setting
Setting values for nozzle and air damper
32
28
24
20
16
12
8
4
0
15
20
25
14
Bentone
30 kW
30 / 11.86*
0.65 GPH
11.0 bar
30 kW
30 x 1.06
31.8/11.86 *
0.75 GPH
9.5 bar
30
35
40
45
50
Burner output, kW
=
2.53 kg/h
=
31.8 kW
=
2.68 kg/h
=
10.0
=
7.0
55
165 205 38

Advertisement