1.Turn off the power button
2.Turn off the battery switch
3.Disconnect the grid supply, the LED light and the battery power display LED light will be
turned off.
6.4 Communication
The Redx unit has an external data collector, users can choose either WIFI or 4G dataloggers
according to their requirements, and use their computer or mobile phone APP (Redx Power) to
monitor the inverter and battery status. The default datalogger in the device uses Wi-Fi
to connect to the customer's Wi-Fi router to establish an Internet connection. The installer will use
Bluetooth to connect to the datalogger and configure the device to connect the datalogger to the
local Wi-Fi router during the installation process.
7 RX-5000AC System Turn On and Turn Off
7.1 Turn on RX-5000AC
You can perform the following steps to start the RX-5000AC:
(1) Turn on the AC and all other relevant circuit breakers.
(2) Turn on the battery circuit breaker.
(3) Turn on the power button.
(4) When the LED display is normal, the system starts normally.
7.2 Turn off RX-5000AC
(1) Turn off the power button.
(2) Turn off the battery circuit breaker.
(3) Turn off the AC and all other relevant circuit breakers.
(4) When the LED display is off, the system is completely off.
(5) Wait at least 60 seconds before performing further operations.
8.1 Troubleshooting
Once a fault occurs in the storage unit, the fault information will be displayed on the APP/web
interface.