An independent circuit breaker must be configured for each power interface.
The table below is a recommendation for cable selection and the Recommended specifications
of circuit breaker. Engineers should refer to local standards to select cables. Cable length
is generally 2 to 10 meters, long cable will lead to voltage deviation from the rated value,
consequently requiring an increase of the cross-sectional area.
Power interface
LOAD
GRID
Note: for details about the electrical connection, see Figure 2-1.2.3

5.1 Battery Connection

1
PE cable
connects to inverter
Battery to Battery PE Cable
Note: Com1 of Bat1 connects to inverter communications port.
Figure 5.1.1 - RX-5000AC Multiple battery interconnection
Rev 20230602

5 Electrical Connection

Table 5.0.1 - RX-5000AC Cabling guide
Circuit breaker Suggestion
>25A
>35A
Battery Connection
2
M6
5 N.M
3
Power Cable
RX - 5000AC
Cross-sectional area (mm2)
≥4 mm2
≥6 mm2
Note:
Com2 of Bat1 connects to
Com1 of Bat2
COM2
BAT1
Communication
Cable
BAT2
COM1
Page 20 of 40