Technical Data - Redx RX Series User Manual

Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

2.4 Technical Data

GENERAL
Internal on/off grid switch
Operating temperature range
Display/indicators
Cooling
Size W*H*T
Weight
IP rating
Protective Class
Altitude
Over Voltage Category
The decisive voltage class
Active anti-islanding method
Inverter Topology
GRID
Rated Output Power
Voltage range
Rated line frequency
Rated Output current
Max AC current
Total THD
Load regulation
Output power factor
Inrush current
Max output fault current
Max output overcurrent protection
LOAD OUTPUT 
Output power (with battery only)
Rated output voltage (off grid)
Frequency (off grid)
Rated output current
Max AC current
Max efficiency (battery to AC output)
Rev 20230602
Yes
-20℃ to +50℃
LED indicators
Convection
620mm X 400mm X 162mm
22.5KG
IP65
Class I
<2000 m
AC:OVC III DC:OVC II Others: OVC I
DC,AC:DVC C,other ports: DVC A
Reactive disturbance
Isolated
5kW
175~280Vac
50Hz/60Hz ±10%
22Aac
25A
<5%
<3%
0.8 leading - 0.8 lagging
26A
80A
25A
5kW
230V (220/230/240 settable)
50Hz/60Hz ±0.01Hz
22Aac
25A
96.00%
RX - 5000AC