8.3 Routine Maintenance

Item
System Clean
Cable Entry
Electrical Connection
The repair of the battery should be carried out or supervised by personnel
with battery knowledge and necessary precautions. Do not mix batteries
of different types and capacities, please use all batteries of the same model.
If the inverter is not used for more than 7 days, turn off the AC input
and battery input switches.
If it has not been used for more than 3 months, turn on the AC input switch
and battery switch, and start the system to replenish the
battery once.
Maintenance of batteries should be carried out or supervised by authorized
personnel and necessary protection measures should be taken. Do not mix
batteries of different types and capacities. All the battery should be the same
model.
If the inverter is not in use for more than seven days, turn off the AC input
and battery input switches.
If it has not been used for more than 3 months, turn on the AC input switch
and the battery switch to start the system to recharge the
battery once.
Check the temperature and dust of the
Storage Unit. Clean the unit enclosure if
necessary.
Check whether the cable entry is insufficiently
sealed or the gap is excessively large; and
reseal the entry when necessary.
Check whether all cables are firmly in place.
Check whether a cable is damaged ( rodents.
Physical damage, weather etc).
Rev 20230104
Method
RX - 5000AC
Period
Six Months to a year
Once a year
Once a year