Phoenix Contact QUINT4-PS/12DC/24DC/5/PT Manual
Phoenix Contact QUINT4-PS/12DC/24DC/5/PT Manual

Phoenix Contact QUINT4-PS/12DC/24DC/5/PT Manual

Dc/dc converter

Advertisement

Quick Links

QUINT4-PS/12DC/24DC/5/PT
DC/DC converter
Data sheet
109369_en_00
1

Description

QUINT POWER DC/DC converters with SFB Technology
and preventive function monitoring ensure superior system
availability.
Powerful
SFB Technology: 6 times the nominal current for 15 ms
Power reserves:
Static boost of up to 125% (P
Dynamic boost of up to 200% (P
Preventive
Comprehensive signaling:
Analog signal, digital signal, relay contact, LED bar
graph
Flexible connection technology
Tried-and-tested screw connection
Fast Push-in connection
All technical specifications are nominal values and refer to a room temperature of 25 °C and 70 % relative humidity
at 100 m above sea level.
© PHOENIX CONTACT
) for a sustained period
N
) for 5 s
N
2021-11-03
Technical data (short form)
Input voltage range
Mains buffering
Nominal output voltage (U
)
N
Setting range of the output voltage
(U
)
Set
Nominal output current (I
)
N
Static Boost (I
)
Stat.Boost
Dynamic Boost (I
)
Dyn.Boost
Selective Fuse Breaking (I
)
SFB
Output power (P
)
N
Output power (P
)
Stat. Boost
Output power (P
)
Dyn. Boost
Efficiency
Residual ripple
MTBF (IEC 61709, SN 29500)
Ambient temperature (operation)
Dimensions W/H/D
Weight
12 V DC -25 % ... +40 %
typ. 4 ms (12 V DC)
24 V DC
24 V DC ... 29.5 V DC
5 A
6.25 A
10 A (5 s)
30 A (15 ms)
120 W
150 W
240 W (5 s)
typ. 91.3 % (24 V DC)
< 20 mV
PP
> 930000 h (40 °C)
-25 °C ... 70 °C
-40°C (startup type tested)
> 60 °C Derating: 2,5 %/K
36 mm / 130 mm / 125 mm
0.6 kg

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUINT4-PS/12DC/24DC/5/PT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Phoenix Contact QUINT4-PS/12DC/24DC/5/PT

  • Page 1: Description

    QUINT4-PS/12DC/24DC/5/PT DC/DC converter Data sheet 109369_en_00 © PHOENIX CONTACT 2021-11-03 Description QUINT POWER DC/DC converters with SFB Technology and preventive function monitoring ensure superior system Technical data (short form) availability. Input voltage range 12 V DC -25 % ... +40 % Mains buffering typ.
  • Page 2: Table Of Contents

    QUINT4-PS/12DC/24DC/5/PT Table of contents Description ..........................1 Table of contents ........................2 Ordering data .......................... 3 Technical data ......................... 5 Safety and installation notes ....................15 High-voltage test (HIPOT) ..................... 17 Structure of the power supply ....................18 Mounting/removing the power supply ..................21 Device connection terminal blocks ..................
  • Page 3: Ordering Data

    TWN4 MIFARE NFC USB 2909681 with USB interface for the wireless configuration of NFC- ADAPTER capable products from PHOENIX CONTACT with software. No separate USB driver is required. Multi-channel electronic circuit breaker for protecting four CBMC E4 24DC/1-4A NO 2906031 loads at 24 V DC in the event of overload and short circuit.
  • Page 4 QUINT4-PS/12DC/24DC/5/PT Accessories Type Item no. Pcs./Pkt. Multi-channel, electronic circuit breaker with active CBM E4 24DC/0.5-10A NO-R 2905743 current limitation for protecting four loads at 24 V DC in the event of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents.
  • Page 5: Technical Data

    QUINT4-PS/12DC/24DC/5/PT Technical data Input data Unless otherwise stated, all data applies for 25°C ambient temperature, 12 V DC input voltage, and nominal output current (I Input voltage range 12 V DC -25 % ... +40 % Electric strength, max. 25 V DC (60 s) Current draw typ.
  • Page 6 QUINT4-PS/12DC/24DC/5/PT Electric strength of the insulation Housing Input Signaling Output Type test ( IEC/EN 61010-1 ) 2 kV DC 4 kV DC 0.5 kV DC 0.5 kV DC Production test 2 kV DC 2 kV DC 0.5 kV DC 0.5 kV DC Input current vs.
  • Page 7 QUINT4-PS/12DC/24DC/5/PT Input connection data Conductor cross section flexible, with ferrule without 0.2 mm² ... 4 mm² plastic sleeve Conductor cross section AWG 24 ... 10 Stripping length 10 mm Output data Nominal output voltage (U 24 V DC Setting range of the output voltage (U ) ( >...
  • Page 8 QUINT4-PS/12DC/24DC/5/PT LED signaling > 100 % LED lights up yellow, output power > 120 W > 75 % LED lights up green, output power > 90 W > 50 % LED lights up green, output power > 60 W > 0.9 x U LED lights up green < 0.9 x U LED flashes green UIn >...
  • Page 9 QUINT4-PS/12DC/24DC/5/PT Remote signal input (configurable) Connection labeling 3.3 + Function Output power ON/OFF (remote) Default Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd) Signal ground SGnd Connection labeling 3.4 + Function Signal ground Reference potential to OUT1, OUT2, REM...
  • Page 10 QUINT4-PS/12DC/24DC/5/PT General data Degree of protection IP20 Protection class Special with SELV input and output Inflammability class in acc. with UL 94 (housing / terminal blocks) Side element version Aluminum Hood version Stainless steel X6Cr17 Dimensions W / H / D (state of delivery) 36 mm / 130 mm / 125 mm Dimensions W / H / D (90°...
  • Page 11 QUINT4-PS/12DC/24DC/5/PT Standards Electrical safety (of control and regulation devices) IEC 61010-1 Protective extra-low voltage EN 61010-1 (SELV) IEC 61010-2-201 (PELV) Mains variation/undervoltage EN 61000-4-29 EMC requirements, power plant IEC 61850-3 EN 61000-6-5 Approvals UL Listed UL 61010-1 CAN/CSA C22.2 No. 61010-1-12 UL Listed UL 61010-2-201 CAN/CSA C22.2 No. 61010-2-201:18 UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) Type tested (type approved) CB scheme (IEC 61010-1, IEC 61010-2-201)
  • Page 12 QUINT4-PS/12DC/24DC/5/PT Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) CE basic standard Minimum normative Higher requirements in requirements practice (covered) Conducted noise emission EN 55016 EN 61000-6-4 (Class A) EN 61000-6-3 (Class B) Noise emission EN 55016...
  • Page 13 QUINT4-PS/12DC/24DC/5/PT Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply) CE basic standard Minimum normative Higher requirements in requirements of practice (covered) EN 61000-6-2 (CE) (immunity for industrial environments) Surge voltage load (surge) EN 61000-4-5...
  • Page 14 QUINT4-PS/12DC/24DC/5/PT Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) Basic standard Minimum normative Higher requirements in requirements of practice (covered) EN 61000-6-5 Asymmetrical conducted disturbance variables EN 61000-4-16 Input, Output, Signals 15 Hz ... 150 Hz , 10 V on 1 V 15 Hz ...
  • Page 15: Safety And Installation Notes

    QUINT4-PS/12DC/24DC/5/PT Safety and installation notes Safety and warning notes Symbols used WARNING: Danger to life by electric shock! Instructions and possible hazards are indicated by corresponding symbols in this document. – Only skilled persons may install, start up, and operate This is the safety alert symbol.
  • Page 16 QUINT4-PS/12DC/24DC/5/PT The continuous total output power may not exceed at 60 °C ambient temperature and P Stat. Boost 40°C ambient temperature. Observe all the maximum output powers for all operating conditions. NOTE: Damage to the Push-in connection terminal blocks is possible Do not plug test pins into the Push-in connection terminal blocks.
  • Page 17: High-Voltage Test (Hipot)

    QUINT4-PS/12DC/24DC/5/PT High-voltage test (HIPOT) Figure 1 Potential-related wiring for the high-voltage test This power supply is subject to the Low Voltage Directive and is factory tested. During the HIPOT test (high-voltage test), the insulation between the input circuit and output circuit is tested for the prescribed electric strength values, for example.
  • Page 18: Structure Of The Power Supply

    QUINT4-PS/12DC/24DC/5/PT Structure of the power supply Device dimensions Figure 3 Device dimensions (dimensions in mm) The fanless convection-cooled power supply can be snapped onto all DIN rails according to EN 60715. Function elements Figure 2 Operating and indication elements Output DC...
  • Page 19 QUINT4-PS/12DC/24DC/5/PT Keep-out areas Nominal output Spacing [mm] capacity < 50 % ≥ 50 % Figure 5 Device dimensions and minimum keep-out areas (in mm) Output DC Signal SGnd Out 1 Out 2 > 100% Boost > 75% > 50% DC OK...
  • Page 20 QUINT4-PS/12DC/24DC/5/PT Block diagram Figure 6 Block diagram Symbol Designation Symbol Designation Surge protection (varistor) with filter Additional regulatory protection against surge voltage Reverse polarity protection Switch Inrush current limitation PNP transistor switch output Switching transistor and main transmitter Microcontroller (electrically isolating)
  • Page 21: Mounting/Removing The Power Supply

    QUINT4-PS/12DC/24DC/5/PT Mounting/removing the power Retrofitting the universal DIN rail adapter supply For installation in horizontal terminal boxes it is possible to mount the power supply at a 90° angle to the DIN rail. Mounting the power supply unit No additional mounting material is required.
  • Page 22 QUINT4-PS/12DC/24DC/5/PT 8.3.2 Mounting the universal DIN rail adapter 8.4.1 Mounting the UWA 182/52 universal wall adapter To mount the universal DIN rail adapter on the left side of the device, proceed as follows: Proceed as follows to disassemble the universal DIN rail...
  • Page 23 QUINT4-PS/12DC/24DC/5/PT 8.4.2 Mounting the UWA 130 2-piece universal wall Fix connection wiring to the power supply adapter Two receptacles for the bundled attachment of the Proceed as follows to disassemble the universal DIN rail connection wiring are integrated in the left and right housing adapter that comes pre-mounted: panel.
  • Page 24 QUINT4-PS/12DC/24DC/5/PT – Shorten the excess length of the cable ties. – Then check again that the connection wiring is properly secured. Figure 15 Shorten protruding ends of the cable binder NOTE: Mechanical damage to the connection wiring caused by friction In extreme ambient conditions, e.g., strong...
  • Page 25: Device Connection Terminal Blocks

    QUINT4-PS/12DC/24DC/5/PT Device connection terminal blocks Output By default, the power supply is pre-set to a nominal output The front-mounted DC input and DC output terminal blocks voltage of 24 V DC. and the signal terminal blocks of the power supply feature The output voltage is adjusted via the two arrow keys (-) Push-in connection technology.
  • Page 26: Output Characteristic Curves

    QUINT4-PS/12DC/24DC/5/PT Output characteristic curves This section describes the various output characteristic curves together with their areas of application for customization to your specific application. The U/I Advanced characteristic curve is set by default. Keeps temperatures Loads with high inrush Selective tripping of...
  • Page 27 QUINT4-PS/12DC/24DC/5/PT 10.1 U/I Advanced output characteristic curve 10.2 Smart HICCUP output characteristic curve The preset U/I Advanced output characteristic curve is The SMART HICCUP output characteristic curve keeps the optimized for the following applications: thermal load of the connecting cables at a low level in the event of a sustained overload.
  • Page 28 QUINT4-PS/12DC/24DC/5/PT 10.3 FUSE MODE output characteristic curve In the event of an overload (e.g., short circuit), the power supply switches off the DC output permanently. The value of the switch-off threshold and the time period for which it may be exceeded can be freely selected. The power supply is restarted via the remote contact.
  • Page 29: Configuring The Power Supply

    QUINT4-PS/12DC/24DC/5/PT Configuring the power supply 11.2 Configuring the power supply To configure the power supply, proceed as follows: With the fourth generation of the QUINT POWER power – Before you can configure the power supply, it should supply, it is now possible for the first time to adapt the either be disconnected from the supply voltage or behavior of the power supply.
  • Page 30: Boost Currents

    QUINT4-PS/12DC/24DC/5/PT Boost currents 11.3 Configuration with NFC-capable mobile The power supply provides the static boost (I ) for a Stat. Boost terminal device sustained load supply or the time-limited dynamic boost The QUINT POWER app enables you to conveniently Dyn. Boost configure the power supply using a mobile terminal device, such as a smartphone.
  • Page 31 QUINT4-PS/12DC/24DC/5/PT Use the following tables to determine the required recovery 12.2.3 Example: Determining the recovery time time (t ) at the maximum dynamic boost current (I Pause Dyn. Pause ) based on the following values: Boost At an output current (I  ...
  • Page 32: Sfb Technology

    QUINT4-PS/12DC/24DC/5/PT SFB Technology 13.3 SFB configuration Observe the following framework conditions for determining SFB Technology (selective fuse breaking) can be used to the maximum distance between the power supply and load: quickly and reliably trip miniature circuit breakers and fuses –...
  • Page 33 The distances given in the table are worst-case values and therefore cover the entire tolerance range for the magnetic tripping of circuit breakers. The possible distances are often greater in practice. 13.4.1 Thermomagnetic device circuit breaker, type: Phoenix Contact CB TM1 SFB Maximum distance l [m] with device circuit breaker Conductor cross section  ...
  • Page 34 QUINT4-PS/12DC/24DC/5/PT 13.4.2 Thermomagnetic circuit breaker, type: Siemens 5SY, ABB S200 Maximum distance l [m] with circuit breaker Conductor cross section   A [mm²] 0.75   (17) Siemens 5SY A1.6 C1.6 ABB S200 Z1.6 The cable lengths determined are based on the following parameters:...
  • Page 35 QUINT4-PS/12DC/24DC/5/PT 13.4.3 Fuse, type: Cooper Bussmann GMA xA, GMC xA Maximum distance l [m] with fuse Melting integral I²t Conductor cross section [A²s]     A [mm²] 0.75     (17) Cooper Bussmann GMA 1A 0.48 GMA 1.25A 0.84 GMA 1.5A GMA 1.6A GMA 2A GMC 1A GMC 1.25A...
  • Page 36: Signaling

    QUINT4-PS/12DC/24DC/5/PT Signaling 14.1 Location and function of the signaling elements Figure 29 Position of signaling elements A floating signal contact and two digital outputs are available for preventive function monitoring of the power supply. Depending on the configuration of the power supply, either...
  • Page 37 QUINT4-PS/12DC/24DC/5/PT 14.1.1 Floating signal contact 14.1.3 Active analog signal output In the default configuration, the floating switch contact The signal output "Out 2" can be used as an analog signal opens to indicate that the set output voltage has been output to continuously monitor the device workload.
  • Page 38 QUINT4-PS/12DC/24DC/5/PT 14.2 Preventive function monitoring In contrast to the default signaling set upon delivery, you can customize this to the specific needs of the system. The following signal options can be selected to signal system states. QUINT POWER default settings upon delivery Out 1...
  • Page 39 QUINT4-PS/12DC/24DC/5/PT 14.3 Description of signaling is true if a control cabinet fan or cooling system fails. In the event of any form of overtemperature, the power supply 14.3.1 Output voltage provides a warning by means of this signal, well before the supply of the loads is in any danger.
  • Page 40 QUINT4-PS/12DC/24DC/5/PT 14.4 Remote input When using a PLC output, select the following external circuit version to switch the power supply to SLEEP MODE. The power supply is switched on and off using the digital remote input of the power supply. When switched off, power...
  • Page 41 QUINT4-PS/12DC/24DC/5/PT 14.6 U/I Advanced characteristic curve signaling The following table shows the standard assignment for signaling for the U/I Advanced characteristic curves which is set by default. Figure 36 Signal image for U/I Advanced 14.7 Smart HICCUP characteristic curve signaling The following table shows the standard assignment for signaling for the Smart HICCUP characteristic curve.
  • Page 42 QUINT4-PS/12DC/24DC/5/PT 14.8 FUSE MODE characteristic curve signaling The following table shows the standard assignment for signaling for the FUSE MODE characteristic curve. Figure 38 Signal image for FUSE MODE 14.9 SLEEP MODE signaling In SLEEP MODE, all LEDs are off, all signals are low, and the relay switching contact is open.
  • Page 43 IEC/EN 61850-3 or signal connection types 3 (process area) and 4 (high voltage area) in accordance with EN 61000-6-5. When using the digital signals, a relay (Phoenix Contact Order No.: 2900299 or a comparable relay) can be implemented. 14.10.2 Surge protection for devices in use in safety-related systems Surge protection (Phoenix Contact Order No.: 2907925 or comparable protection) must be implemented for railway...
  • Page 44: Operating Modes

    QUINT4-PS/12DC/24DC/5/PT Operating modes 15.2 Parallel operation You can connect several power supplies in parallel in order 15.1 Series operation to increase the power or to supply the loads redundantly. To double the output voltage, connect two power supplies in Figure 42 Schematic diagram in parallel operation series.
  • Page 45 QUINT4-PS/12DC/24DC/5/PT 15.2.1 Redundancy operation maximum half the nominal power. The keepout areas are therefore reduced. Redundant circuits are suitable for supplying systems and Using the signaling settings, you can monitor whether both system parts which place particularly high demands on power supplies are being operated with ≤...
  • Page 46: Derating

    QUINT4-PS/12DC/24DC/5/PT Derating 16.2 Installation height The power supply can be operated at an installation height The QUINT POWER power supply runs in nominal of up to 2000 m without any limitations. Different data operation without any limitations. For operation outside the applies for installation locations above 2000 m due to the...
  • Page 47 QUINT4-PS/12DC/24DC/5/PT 16.3 Position-dependent derating The fanless convection-cooled power supply can be snapped onto all DIN rails according to EN 60715. The power supply should be mounted horizontally for heat dissipation reasons (DC connection terminal blocks facing downward). Please observe the derating for any mounting other than the normal mounting position. Reduce the output power based on the prevailing ambient temperature.
  • Page 48 QUINT4-PS/12DC/24DC/5/PT 16.3.3 Rotated mounting position 180° Z-axis 16.3.4 Rotated mounting position 270° Z-axis 109369_en_00 PHOENIX CONTACT 48/49...
  • Page 49 QUINT4-PS/12DC/24DC/5/PT 16.3.5 Rotated mounting position 90° X-axis 16.3.6 Rotated mounting position 270° X-axis PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 109369_en_00 49/49 phoenixcontact.com...

This manual is also suitable for:

2910124