Setpoint Values For Monitoring The Bearing Temperature; Further Documents - Siemens SIMOTICS XP 1MB155 Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Start-up
7.1 Measures before commissioning
7.1.5

Setpoint values for monitoring the bearing temperature

Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7- 2
Set value
Alarm
Shutting down
Normal operation
Determine the maximum operating temperature of the bearings T
the temperature, bearing load and influences of the plant on the motor in °C. Set the values
for shutdown and warning corresponding to the operating temperature T
Table 7- 3
Set value
Alarm
Shutting down
7.1.6

Further documents

Note
Further documents
Observe all of the other documents provided with this machine.
88
Set values for monitoring the bearing temperatures before commissioning
Set values for monitoring the bearing temperatures
Temperature
115 °C
120 °C
taking into account
operation
.
op
Temperature
T
+ 5 K ≤ 115 °C
operation
T
+ 10 K ≤ 120 °C
operation
Operating Instructions, 03/2018, A5E41926185A