SIEMOSYN
SIEMOSYN
1FU8
Baugrößen (BG) / Frame sizes (FS)
BG/FS 71 ... 90 L - IM B3
oder
or
IM V 5
IM B 3
IM B 6
IM B 7
Fig. 1
Bauformen / Types of construction
Ausgabe / Edition 08.02
Siemens AG 2002 All Rights Reserved
â
- MOTOREN
â
MOTORS
oder
or
IM V 6
IM B 5
IM B 8
BG/FS 112 ... 160 L - IM B3
IM V 1
IM V 3
IM B 14
Bestell - Nr. / Order No.: 1 610 41390 02 000
Betriebsanleitung
Operating instructions
oder
IM V 18
or
IM B 35
IM B 34
IM V 19
DEUTSCH / ENGLISH
1

Advertisement

Chapters

Table of Contents
loading

Summary of Contents for Siemens SIEMOSYN 1FU8

  • Page 1 IM B 8 IM B 6 IM B 7 Fig. 1 Bauformen / Types of construction Bestell - Nr. / Order No.: 1 610 41390 02 000 Ausgabe / Edition 08.02 DEUTSCH / ENGLISH  Siemens AG 2002 All Rights Reserved...
  • Page 2 Warndreieck bedeutet, daß ein Sachschaden eintreten kann, wenn die entspre- chenden Vorsichtsmaßnahmen nicht getroffen werden. ACHTUNG bedeutet, daß ein unerwünschtes Ereignis oder Zustand eintreten kann, wenn der ent- sprechende Hinweis nicht beachtet wird.  Siemens AG 2002 All Rights Reserved...
  • Page 3: Table Of Contents

    Weiterhin sind die jeweils geltenden nationalen, örtlichen und anlagenspezifischen Bestimmungen und Erfordernisse zu berücksichtigen. Sonderausführungen und Bauvarianten können in technischen Details abweichen: Bei eventuellen Unklarheiten wird dringend empfohlen, beim Hersteller rückzufragen, oder die Instandhaltungsarbeiten von einem der SIEMENS- Servicezentren durchführen zu lassen. Haftungsausschluß...
  • Page 4: Allgemeine Sicherheitshinweise

    Für nachträglich reklamierte Mängel übernimmt Siemens keine Gewährleistung. Reklamieren Sie: - erkennbare Transportschäden sofort beim Anlieferer - erkennbare Mängel/unvollständige Lieferung sofort bei der zuständigen SIEMENS-Vertretung. Die Betriebsanleitung ist Bestandteil des Lieferumfanges und somit zugänglich aufzubewahren.  Siemens AG 2002 All Rights Reserved...
  • Page 5: Technische Daten

    Rundlauf, Koaxialität, Planlauf: DIN 42955; Toleranz N Lager: Wälzlager mit Lebensdauerschmierung (Fett) Spannung, Frequenzzuordnung: gem. Leistungsschild Magnetmaterial AH 71 - AH112 Seltenerdmagnete AH132 - AH160 Ferritmagnete Weitere technische Kennwerte, Motoroptionen sowie Maßblätter siehe Katalog.  Siemens AG 2002 All Rights Reserved...
  • Page 6: Aufstellung, Montage

    Schutzleiteranschluß und den äußeren Erdungsleiter (siehe Fig. 6.2) - grüngelb. - Anziehdrehmomente für Schraubenverbindungen der elektrischen Anschlüsse - Klemmenbrettanschlüsse (außer Klemmleisten)siehe Fig. 5. - Anziehdrehmomente für sonstige Schraubenverbindungen (siehe Fig. 5.2). - Anziehdrehmomente für Verschraubungen (siehe Fig. 5.1)  Siemens AG 2002 All Rights Reserved...
  • Page 7: Schwingung, Wuchtung

    - Vorschriften für Arbeiten in elektrotechnischen Anlagen sind unbedingt einzuhalten, gem. DIN VDE 0105 z.B.: + Freischalten + gegen Wiedereinschalten sichern + Spannungsfreiheit sicherstellen + Erden und Kurzschließen + benachbarte unter Spannung stehende Teile abdecken oder/und abschranken + Motor auf Stillstand überprüfen  Siemens AG 2002 All Rights Reserved...
  • Page 8: Inbetriebnahme

    Der Mindestisolationswiderstand der Wicklungen gegen Masse wird mit 500V Gleichspannung gemessen. Dabei soll die Temperatur der Wicklungen 25°C ±15°C betragen. Der kritische Isolationswiderstand ist bei der Betriebstemperatur der Wicklung mit 500V Gleichspannung zu messen.  Siemens AG 2002 All Rights Reserved...
  • Page 9: Anbauten

    SIEMOSYN-Motor 1FU8 mit Federkraftbremse 2LM8 b) SIEMOSYN-Motor 1FU8 mit Demag Getriebe (mit/ohne Bremse 2LM8) c) SIEMOSYN-Motor 1FU8 mit Frequenzumrichter Micromaster MM411 (mit/ohne Bremse 2LM8) d) SIEMOSYN-Motor 1FU8 mit Demag-Getriebe und mit Frequenzumricher Micromaster MM411 (mit/ohne Bremse 2LM8)  Siemens AG 2002 All Rights Reserved...
  • Page 10: Inspektion, Wartung

    Aussage zu Lagerlebensdauer und Lagerausführung sowie Fettgebrauchsdauer und Fettsorte getroffen werden. Für die spezifischen Betriebsbedingungen (Drehzahl, Querkraft, Kühlmitteltemperatur,...) sind die relevanten Gebrauchsdauern für Lager und Fett bzw. die Nachschmierfrist auf Anfrage erhältlich.  Siemens AG 2002 All Rights Reserved...
  • Page 11: Ersatzteile

    Explosionsdarstellung der Motoren (Fig.2) incl. Auflistung der Ersatzteile 1.40 Lagerschild Bestellbeispiel 1FU8 096-4TA61-Z Nr. E 0204/255 681 02 001 Entsorgung Entsorgung der Motoren unter Einhaltung der nationalen und örtlichen Vorschriften im normalen Wertstoffprozess.  Siemens AG 2002 All Rights Reserved...
  • Page 12 DANGER means that an unexpected event or state can occur if the appropriate note is not observed  Siemens AG 2002 All Rights Reserved...
  • Page 13 Furthermore, the corresponding valid national, local and system-based specifications and requirements are to be met. Special designs and construction versions can deviate in technical details: With possible ambiguity it is urgently recommended to consult the manufacturer or let repair work be executed by one of the SIEMENS Service Centers. Exclusion of liability Contents of the brochure were checked.
  • Page 14: General Safety Information

    SIEMOSYN-motors can be supplied also as drive unit, mounted with transmissions, frequency converters Micromaster MM411, brake… Siemens does not take over any guarantee for subsequent complaints of defects. Complaints are to be made about: - detectable transport damages immediately to the supplier - detectable defects/uncomplete delivery immediately to the relevant SIEMENS agency.
  • Page 15: Technical Data

    Voltage, frequency calssification: acc. to rating plate Magnet material FS 71 - FS112 Rare earth magnets FS132 - FS160 Ferrite magnets Further technical characteristic values, motor options as well as dimensional sheets see catalogue.  Siemens AG 2002 All Rights Reserved...
  • Page 16: Installation, Assembly

    (see fig. 6.2) – green yellow. - tightening torques for bolted joints of the electrical connections-terminal board connections (with the exception of terminal strip) see fig. 5.  Siemens AG 2002 All Rights Reserved...
  • Page 17: Oscillation, Balance

    - the regulations for works in electrotechnical systems are absolutely to be adhered to, acc. to DIN VDE 0105 e.g.: + disconnecting + protect against restarting + ensure dead circuit + earth and short-circuit + cover or/and barrier neighbouring energized sections + check motor for standstill  Siemens AG 2002 All Rights Reserved...
  • Page 18: Commissioning

    Calculation takes place by multiplication of the highest rated krit voltage U (voltage with f ), e.g. AC 400V, with the constant factor (o,5 kOhm/V): R = 400 V x 0,5 kOhm/V = krit 200 kOhm  Siemens AG 2002 All Rights Reserved...
  • Page 19 At motors with installed sensors (e.g. PTC-resistors) interference voltages may occur on the sensor line due to the converter. The operator must provide for sufficiant interference resistance by a suitable selection of the sensor signal lead (if necessary with screening, connection as with motor supply lead) and the tripping unit.  Siemens AG 2002 All Rights Reserved...
  • Page 20: Attachments

    DANGER Caution: Risk of injury: Protect open stored rotors against striking together or striking against metal parts (rotors are magnetic). In the proximity of a disassembled rotor, persons with cardiac pacemakers are endangered.  Siemens AG 2002 All Rights Reserved...
  • Page 21: Bearing

    Explosion representation of the motors (fig.2) incl. listing of the spare parts Disposal Disposal of the motors to take place subject to compliance with the national and local regulations in the normal recycling process.  Siemens AG 2002 All Rights Reserved...
  • Page 22 5.91 (DIN 7985) (DIN 933) DIN 471 7.12 5.94 DIN 625 6.29 1.60 Lagertyp: 7.49 6.10 Type of bearing: DIN 472 6.02 4.04 (s. Fig. 3) DIN 580 3.38 DIN 6885 Fig. 2  Siemens AG 2002 All Rights Reserved...
  • Page 25 Screwed connections with nut (e.g. DIN EN 50262) O-Ring O-Ring O-ring O-ring Mutter Mutter Reduktionsstück Adapter Anschlußkastenwand Wall of terminal box Einbaulage Blechmutter Installation length sheet metal nut Ausbrechöffnung (Gußhaut) Cast iron skin  Siemens AG 2002 All Rights Reserved...
  • Page 26 Connecting a single conductor with Connecting two conductors of al- cable lugs, under the outer ear- downwards. a terminal clip. most equal thickness with a terminal thing angle. clip. Fig. 6.1 Fig. 6.2  Siemens AG 2002 All Rights Reserved...
  • Page 27 - according to the catalog - transmitted to the motor bearings through the shaft extension. Fig. 9 Auswuchtung mit halber Paßfeder Balancing with half featherkey  Siemens AG 2002 All Rights Reserved...
  • Page 28 D-97616 Bad Neustadt an der Saale Änderungen vorbehalten / Subject to change without prior notice Bestell-Nr. / Order No.: 1 610 41390 02 000 Siemens Aktiengesellschaft Printed in the Federal Republic of Germany 08.02 De-En  Siemens AG 2002 All Rights Reserved...