Technical Data - Window Master CompactSmoke WSC 104 S AR Installation Instructions Manual

Table of Contents

Advertisement

Smoke detector
Rain sensor
Rain/wind speed sensor
End of line motor module
End of line smoke detector module (10kΩ resistor), 10 pcs.
Cable glands
Cables for smoke ventilation – see separate data sheet for further information
Comfort keypad for 1 window or 1 window group
4A power supply unit for WSC 104
Main card incl. cover
Replacement glass for break glass units' type WSK 501 / 502 / 503 / 504, 5 pcs.
Keys for break glass units' type WSK 501 / 503, 5 pcs.
Keys for break glass units' type WSK 502 / 504, 1 pcs.
Lockable replacement PVC housing for break glass unit
x=colour of the housing: 1 = red, 2 = yellow, 3 = grey, 5 = orange

Technical data

5
Output current (nominal)
Secondary voltage
AUX
Motor lines
Smoke zones
Primary voltage
Power consumption
Leakage current
Inrush current on primary site
±24V change over time
Back-up batteries
Emergency power
Charging unit (integrated in WCA 1SS
card)
Priority
Cable monitoring
Spare parts
Technical data
4A
Voltage
Open circuit voltage (no load)
Ripple at max load
24V DC, 500mA
1 motor line – the line can be either ±24V standard motor line or MotorLink
motor line. 1 smoke zone.
230V AC, 50Hz (85-264V AC, 47-63Hz)
2
1
min 0.3W
, typ. 0.2W
. At max load 110W
1) min. config. idle: 1 x break glass unit WSK 501 and 1 x smoke detector
WSA 311, system operational but no actuators are running
2) min idle:
1 x break glass unit WSK 501, 4 x break glass unit WSK 503, 4 x
smoke detector WSA 311 and 1 x rain sensor WLA 330
3) max load: 1 x break glass unit WSK 501, 4 x break glass unit WSK 503 and
10 x smoke detector WSA 311 in alarm
Max 1.4mA @ 240VAC
50A / 230VAC
Max. 7 x WSC 104 per 10A supply group.
Circuit breaker "C" characteristic.
min 500ms
2 x WSA 003 (12V / 3.4A),
Expected lifetime max 4 years, only use genuine WindowMaster batteries
>72 hours in accordance with EN 12101-10
Charging voltage: 27.7 – 27.8V at 20ºC
Charging current: 700mA current limited
Smoke signal has always highest priority
±24V standard actuators with end of line module and smoke detectors are
monitored.
®
Actuators with MotorLink
communication.
Back-up batteries are monitored by cyclic measuring
24V DC (±15%)
24V DC @ 20°C
150mVp-p
3
and break glass units are monitored by data
WSA 311
WLA 331
WLA 330
WSA 514
WSA 501
WSA 133
WLL 8xx
WSK 110 0A0B
WCA 1P1
WSA 1SS
WSK 397
WSK 398
WSK 453
WSK 399 000x
®