Technical Description; Wsc 204Kp - Window Master WSC 204 Operating Manual/Technical Information

Smoke control panel
Table of Contents

Advertisement

2. Technical description

Function
Supply voltage
Safety transformer
Power consumption
Actuator secondary voltage
Inrush current
Standby consumption
Switch time between 230V- and
battery operation
Emergency power supply
batteries
Charging unit:
Operating duration (emergency
power supply )
Current load of the actuators
(battery and 230V operation)
Current load of the smoke unit
(batteries, surveillance, periphery)
Switch-on duration
Reopening the actuators
Review of fuses
Type of connection to external
Cable monitoring
Message OK, fault and alarm
Automatic smoke triggering
Operating conditions
Approval / Certification
Protection type
WSC 204 / WSC 204KP / WSC 204MH
Opens the window actuators when triggered by a SHE-signal caused by smoke
detector or break glass unit.
WSC 204BZ
Closes the window actuators when triggered by a SHE-signal caused by smoke
detector and opens the actuators when activating a break glass unit.
230V AC / 50/60Hz ((±10%))
according EN 61558
max. 150VA
rated voltage
open circuit voltage at 230 VAC
open circuit voltage at 253VAC
actuator voltage at 230 VAC / 4.8A load
ripple at full load (4.8A)
open circuit voltage at battery operation
Max 6A<5msec
4W
max 2.5sec
2 x 12V / 3,4Ah. Expected lifetime 4 years. (2pcs. WSA 003). Only use genuine
WindowMaster back up batteries.
Charging voltage: 27,7 – 27,8 at 20ºC
Charging current: 350mA, current limited
72 hours if batteries are fully charged (1,9Ah)
max. 4,8A
max. 0,7A
40% ED
during the first 30 min. after a SHE-trig the actuators cyclically every 2 min.
mains 1A slow-blow
actuator fuse 5A slow-blow
battery 630mA medium slow-blow
mains screw terminal / plug-screw terminals / 0.5-2.5mm²
automatic detectors (detector circuit with active end module), break glass unit
(detector circuit with end resistor), actuators (with motor end module), batteries
(cyclic measurement)
optically alternating or steady signals by LED's:
steady green LED = operating
alternating yellow LED = malfunction of battery(at battery voltage less than 19V
or above 29V), actuator, break glass unit or smoke
steady red LED = alarm (short circuit)
Smoke triggering when temperature inside the compact unit exceeds 72°C
-5°C - 40°C, max. 90% relative humidity (not condensing)
WSC 204 / WSC 204KP / WSC 204BZ: approved according to EN12101-10
WSC 204 / WSC 204KP / WSC 204BZ
IP 30 (plastic housing)
WSC 204MH
IP54 (steel housing)
24V
typ. 28V DC
max 31.3V DC
typ. 22V DC
max. 6% (= 3.8Vpp)
min 18.7V DC
4