Pyrotechnic gas generator or electromagnetic release
When a pyrotechnic gas generator or an electromagnetic release is connected to the smoke panel, DIP-switch 8
must be set to ON, see "DIP-Switch configuration".
A pyrotechnic gas generator is connected to the smoke panel via the motor line and PE.
An electromagnetic release is connected to the smoke panel via the motor line.
An end of line motor module (WSA 514) is not to be connected when pyrotechnic gas generators or
electromagnetic releases are connected.
Max 12 pyrotechnic gas generators or max 10 electromagnetic releases can be connected to the smoke panel.
IMPORTANT an auto configuration is not to be carried out when pyrotechnic gas generators nor electromagnetic
releases are connected!
When DIP switch 8 is changed from ON to OFF and neither pyrotechnic gas generators nor electromagnetic
releases are connected, an auto configuration must be performed.
Note Connection of pyrotechnic gas generators or electromagnetic releases requires firmware version from 1.04.
X3
For connection of comfort keypads. X3 is potential free / dry contact.
Data
3.1 Open
3.2 Close
3.3 GND / 0V
With the default values are input:
"Active" if the contact resistance is smaller than 2kΩ
"Inactive" if the contact resistance is bigger than 3kΩ.
Input has pull up current of approx. 0.8mA. (min. 0.7mA, max 1mA)
Example: comfort keypad connected to input X3
Open circuit (simplified)