X8
Solid state output for transmission of fault signal to Fire Alarm System
Data
8.1
Normally closed. Open = Fault
8.2
Solid state output for transmission of fault signal to Fire Alarm System.
A fault must last min 20 seconds before the relay indicate a fault.
Data
Max voltage: 30 Vp (peak)
Max output: 150 mA
Typical On-resistance: 4,7 Ω
Max On-resistance: 8 Ω
Max switching speed: 2 ms
X9
For connection of rain sensor.
Connection of wind / rain sensors type WLA 330 or rain sensor WLA 331.
Data
9.1 24V
9.2 Rain (potential free / dry contact) (10kΩ resistor is to be moved to the
Rain sensor)
9.3 GND / 0V
With the default values are input:
"Active" if the contact resistance is smaller than 4kΩ
"Inactive" if the contact resistance is bigger than 8kΩ.
For values between 4 and 8kΩ the result will depend on the supply voltage.
Input has pull up 17pprox.. 1mA. (min. 0.7mA, max 1.4mA)
Example: Wind/rain and rain sensors
WLA 330 and WLA 331– the settings of the sensors are set on the sensor.
J3
Connection for power supply
J4
USB device. Used for remote control and update of firmware
J5
No function
J6
Connection for battery (power back-up)
R / P
Reset / Programming (used for firmware updates)
DS
DIP switch blocks with 8 DIP switches
1 – No 230V window position unchanged
2 – Momentary action open / close
3 – Re-triggering by alarm (VdS)
4 – Automatic reset after alarm
5 – Open / close on fire
6 – Limited opening comfort ventilation
7 – Time comfort ventilation
8 – Pyrotechnic gas generator
See section 11 for further detail