Shows the status of the panel
Red
= alarm
LED
Yellow = fault
Green fast flickering = all OK (CPU working), Green constant = CPU communication stopped (possible reset or
contact WindowMaster)
Close / open all windows. When pressed together right after power has been connected the panel configures /
↓ ↑
registers connected components.

DIP switch configuration

11
For easy configuration the smoke panel includes 8 DIP switches. The factory settings for all the DIP switches is OFF.
DIP
Description on
switch
the panel
1
No 230V
window pos.
unchanged
2
Moment. act.
Open / Close
3
Re-triggering
(VdS)
4
Automatic reset
after alarm
5
Open / Close on
fire
6
Limited opening
comfort. vent
7
Time comfort
vent.
8
Pyrotechnic gas
generator
Description
No 230V window
ON: No change in position in case of power
position unchanged
failure
OFF: The windows close in case of power
failure.
Momentary action
ON: The window actuators run for as long as
OPEN / CLOSE
the comfort keypad is pressed. Applies only to
(Comfort ventilation)
comfort keypads connected to X3.
OFF: The windows close / open completely
when pressing the comfort keypad once.
VdS triggering by
ON: When the alarm is triggered the actuators
alarm
will, in accordance with VdS 2581, for a
duration of 30min be triggered to shortly
reverse and open every second minute.
OFF: Normal alarm
The panel is
ON: The panel must manually be reset after
automatically reset
the alarm has been triggered.
after the alarm signal
on terminal X6 has
OFF: The panel is automatically reset after the
been deactivated.
alarm has been deactivated.
Note that the alarm
from the break glass
unit is not affected by
this DIP switch.
The windows open or
ON: The windows close in case of fire
close in case of fire
OFF: The windows open in case of fire
Window opening is
ON: The window opening is limited to 30%
limited
during comfort ventilation
(Only by comfort
ventilation)
OFF: The windows will open 100% during
comfort ventilation
Window opening is
ON: The windows will close after 30min during
time limited
comfort ventilation
(Only by comfort
ventilation)
OFF: The windows will close when triggered
by safety signal or close command
Pyrotechnic gas
ON: A pyrotechnic gas generator is connected
generator is
connected
OFF: Window actuators are connected
When DIP switch 8 is changed from ON to
OFF the panel must be re-configured, see
section 13 "Configuring of panel".
DIP switch position
Possible
consequence
This function
becomes suspended
when DIP switch 2 is
ON.