Back-up batteries
12
Connect 2 pcs. back-up batteries type WSA 003
See section 17 "Maintenance" for further
information.
Configuration of panel
13
The smoke panel is configured by pressing the two keys "↑" and "↓" on the main card, at the same time for 5-10 seconds.
The smoke panel must be configured
-
After re-installation, changes, or change of actuators
-
When / if MotorLink
-
If the cables have been moved
-
When components are removed from the panel
-
If there has been a fault on the WSK-Link™. Error blink sequence 6, see section 14.1.
-
When DIP switch 8 is changed from ON to OFF
Note, during reconfiguration the actuator output can be activated in both directions.
If the yellow diode on the main card blinks after a configuration, an error has occurred in the configuration, see section 14 "Fault
detection via LED" for identification of errors.
13.1.1 Motor line
Actuators are to be connected on the motor line. ±24V standard actuators or actuators with MotorLink
motor line, the motor line can only be connected to one type of actuators – either ±24V standard or MotorLink
panel will automatically detect the type of actuator, which is connected to the panel.
13.1.2 Smoke zone
Depending on the settings on the DIP-switches the actuators will either open or close when the smoke panel is triggered, see
section 11.
13.1.3 Local input
The four inputs on the panel are pre-configured with the functions as shown below.
X3 Comfort keypads
X5 Break glass unit
X6 Smoke detector
X9 Rain sensor
®
actuators are connected
Panel with back–up batteries.
®
can be connected to the
®
actuators. The