LED message OK, fault and alarm
Reopening the actuators
Connection cable
Operating conditions
Max actuator activation duration (duty
cycle)
Max allowed current drawn from the
battery when the primary power
source is disconnected
Max interruption time during switching
between power sources
Break glass unit
Number of motor lines
Material
Colour
Size
Weight
Protection class
Approval / certification
Delivery
Note

Mounting

6
The smoke ventilation panel is fixed to the wall through the Ø6.5mm holes in the back plane of the
housing.
The smoke ventilation panel is to be located in a safe place, protected from the effects of fire and
smoke.
Green
all OK
Yellow
fault
Red
fire
Every 2.min. in 30min. after a SHE open (selectable) Pre-set: no reopening
Actuators
flexible max 6 mm² / solide max 10 mm²
Other
min 0,2mm² / max 1,5mm²
components
-5°C - +40°C, max. 95% relative humidity (not condensing)
EN 12101-10: Operation class A, Environmental class 1, IP30
ED 40% (4min. per 10min.)
4A incl. AUX
The total current consumption may not exceed 4A incl. load on AUX (max.
500mA)
<2.0sec
Up to 5 break glass units type WSK 50x can be connected to the panel, but only
1 WSK 501 / 502 per panel.
Smoke detectors and ventilation keypads can only be connected to the break
glass units type WSK 501 / 502. Smoke detectors and ventilation keypads cannot
be connected to WSK 503 / 504.
Up to 10 smoke detectors can be connected to the system. Smoke detectors can
either be connected to the WSK 501 / 502 and/or the smoke detector input on the
main card.
There is no limit on the number of ventilation keypads connected to the WSK 501
/ 502.
1 x 4A motor line for ±24V standard or MotorLink
Plastic housing for surface mounting
White (RAL 9016)
224 x 283 x 85mm (H x W x D)
1.2kg no batteries, 4kg with batteries (2 x WSA 003)
IP30
Approved and certified according to EN 12101-10
CompactSmoke™ smoke ventilation panel, 4 x 10kΩ resistors, 1 x WSA 514 end
of line module. Back-up batteries included.
We reserve the right to make technical changes
®
actuators
7