Furthermore, when using a 5-core cable, the
distance between "–" and "Com" must be the same
as the distance between "+" and "Com".
Meaning if L2 e.g. is being used as "Com" L1 and L3
must be used for "+" and "-".
When using actuators with MotorLink
cable cross
section [a]
Total
actuator current [I]
1A
2A
3A
4A
Definition of total cable length
The total cable length is defined as
the sum of all cables from the panel
output to the last actuator. Including
the cable mounted on the actuator.
For example, in case of 4 actuators
with 5m cable each, the remaining
cable length is 30m.
8.2.4 Max cable length – Pyrotechnic gas generator
cable cross
section [a]
Total
actuator current [I]
1A
flexible stranded cores are only suitable with attached ferrules. Max 1 core / ferrule per terminal.
*
**WSC 104 has been tested with Chemring type 1.3.
®
the max/total cable length is 50m regardless of the result of the above mentions formula.
Actuators with MotorLink
Do not use the PE wire / green/yellow wire!
3 wire
3 wire
0.75mm²
1.50 mm²
42m
21m
40m
14m
28m
11m
21m
Pyrotechnic gas generator**
Do not use the PE wire / green/yellow wire!
3 wire *
3 wire *
0.75mm²
1.50 mm²
42m
84m
®
5 wire
3 wire
1.50 mm²
2.50 mm²
2 wire
parallel
50m
47m
42m
35m
5 wire
3 wire *
1.50 mm²
2.50 mm²
2 wire parallel
168m
140m
5 wire
3 wire
2.50 mm²
4.00 mm²
2 wire
parallel
50m
50m
50m
5 wire
3 wire *
2.50 mm²
4.00 mm²
2 wire parallel*
280m
224m
10