User and display parameters (Password 009)
Parameter
Description
UP 00
Enable access to operation modes
UP 01
Enable access to set points
UP 02
Enable manual control in cascade
UP 03
Enable change of heating/cooling mode for 2 pipe systems
UP 04
Enable access to time programs:
State after power failure:
UP 05
0= off, 1= on, 2= state before power failure
Enable Unoccupied (economy) Mode.
Shift the setpoint to a lower temperature in winter or higher temperature
in summer in order to save energy. Unoccupied (economy) mode may be
UP 06
activated through the POWER button, or with the external input (typically
for key card switches in hotel rooms or motion detectors for meeting
rooms.)
UP 07
Celsius or Fahrenheit: ON= Fahrenheit, OFF= Celsius
UP 08
Show standard display while no key is pressed
Select type of content for large digits (00= OFF):
01= Input
UP 09
02= Setpoint
03= Analog Output
Select content source for large digits (0=OFF):
Input:
1= 1T
UP 10
2= 1H
3= 1U
4= 2T
UP 11
Select type of content for small digits(same options as UP09)
UP 12
Select content source for small digits (same options as UP10)
Select analog output for vertical bar display (00= OFF):
UP 13
01= AO1
02= AO2
UP 14
Display heating/cooling state in standard display mode
ON = Alarms blink after being active and need to be confirmed
UP 15
OFF= Alarms are only shown when they are active
UP 16
Clock display type: OFF= 24-hr, ON= 12-hr(AM/PM)
(TCI-W23)
Reset timer for manual override of PRO time schedule:
0= Not active
UP 17
1–255= Delay for controller to go back to the scheduled Energy Hold OFF,
(TCI-W23)
Unoccupied (ECONOMY), or Occupied (COMFORT) operation mode if the
operation mode is changed manually.
UP 18
OFF = Backlight switch on for 30 seconds when a key is pressed.
(TCI-W23)
ON = Backlight switch on constantly when device is in ON mode
Doc: 70-00-0365C, V2.0, 20220523
Subject to alteration
04= Binary Output
05= Clock
Set point:
Analog or
1= Lp1
floating output:
2= Lp2
1= AO1
2= AO1
03= Output LP1
04= Output LP2
© Vector Controls GmbH, Switzerland
TCI-W13, TCI-W23 Universal Controller
U
Binary output:
1= DO1
C
SER
ONFIGURATION
Range
Default
ON/OFF
ON
ON/OFF
ON
ON/OFF
ON
ON/OFF
ON
ON/OFF
ON
0, 1, 2
2
ON/OFF
ON
ON/OFF
OFF (Celsius)
ON/OFF
ON
0–5
1
0–4
1
TCI-W13 = 2
0–5
TCI-W23 = 5
0–4
1
0–4
3
ON/OFF
OFF
ON/OFF
ON
ON/OFF
OFF(24hr)
0–255
60(Min)
Min
ON/OFF
OFF
Page 10-22