Recommended Set-Up Procedure; Setting The Parameters - Vector 40-10 0259 Manual

Wall mounted universal controller
Table of Contents

Advertisement

Setting parameters to configure the controller
TCI is an intelligent controller with the flexibility to fit a wide range of applications. The control operation is defined by
parameters set using the standard operation terminal. There are two levels:
1.
User/display parameters (password 0009)
2.
Control parameters (password 00241)

Recommended set-up procedure

1.
Set jumpers on the back of the controller for inputs and outputs
2.
Connect power supply and inputs
3.
Make sure Celsius – Fahrenheit settings are correct (UP07)
4.
Program input parameters
5.
Program control parameters
6.
Program output parameters
7.
Program auxiliary functions and user settings
8.
Test function of unit
9.
Switch off power
10. Connect outputs
11. Test control loop

Setting the Parameters

Parameters are grouped according to modules.
Module
Description
UP
User and display parameters
1T, 1H, 1U, 2U
Input configuration
Lp1, Lp2
Control loops
AO1
Analog output configuration
do1, do2
Binary output configuration
FU
Special functions
How to change parameters
1.
Press UP/DOWN  buttons simultaneously for three seconds. The display will show firmware version and revision
number.
2.
Press the RIGHT ⚫ button to start login. CODE is shown in small display.
3.
Code to access user parameters is 0009, control parameter is 0241. The access numbers are fixed and cannot be
changed.
4.
Select correct password using UP/DOWN  buttons.
5.
Press RIGHT ⚫ button after selecting the correct code.
6.
Once logged in with 0009, the user/display parameters (UP) are displayed immediately.
Once logged in with 0241 control modules are displayed (Lp1, Lp2, 1u, 2u, etc.) –select with UP/DOWN  and open
with RIGHT ⚫. As soon as the module is open its parameters are displayed.
7.
Select the parameters with the UP/DOWN  buttons. Change a parameter by pressing the RIGHT ⚫ button. The
symbol
is displayed to indicate that the parameter may be modified. Use UP/DOWN  buttons to adjust the
value.
8.
After you are done, press RIGHT ⚫ button to save the new value and return to the selection level (symbol
disappears after selection is saved). Pressing left hand POWER
value and return without saving. For control parameters press POWER
return to control module selection.
9.
Press the POWER
to leave the menu. The unit will return to normal operation if no button is pressed for more than
5 minutes.
Doc: 70-00-0365C, V2.0, 20220523
Subject to alteration
TCI-W13, TCI-W23 Universal Controller
Notes
Control user access and select display elements,
regional settings
TCI-W23: Internal temp. and RH, 2 universal inputs
TCI-W13: Internal temp. 1 universal input
TCI-W23: 2 independent control loops
TCI-W13: 1 independent control loop
1 analog output
2 binary (digital) outputs - relays
Common to all TCI
button without pressing RIGHT ⚫ will discard the
© Vector Controls GmbH, Switzerland
S
C
ETUP AND
ONFIGURATION
again to leave parameter selection and
PW
0009
0241
Page 9-22