Vector 40-10 0259 Manual page 20

Wall mounted universal controller
Table of Contents

Advertisement

Heating/cooling mode changeover
Parameter
Description
Fu 20
Select heat/cool changeover input (0=function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2T, 5= h/c status loop 1,
6= h/c status loop 2
Fu 21
Cooling activation delay (seconds)
Fu 22
Input limit 1
Fu 23
Input limit 2
Switch heating/cooling state based on a universal input value. The input may be from a supply media (air or water)
or outdoor air temperature sensor. For supply media temperature we recommend switching to cooling at 16°C/61°F
and to heating at 28°C/83°F. For outdoor temperature we recommend switching to cooling at 28°C/83°F and to
heating at 16°C/61°F outdoor temperature. These recommendations are given as suggestions. The ideal settings may
be different on the actual project depending on climatic and system conditions.
The change between heating and cooling is delayed to avoid unnecessary switching (FU21). Heat/cool status of one
control loop may also be determined by the heat/cool state of the other loop (FU20= 5 or 6). The control loop used to
determine the heat /cool state must be set to demand-based heating and cooling with (L23). Set limit 1 and limit 2 to
switch between heating and cooling with options below. Example: When Limit 2 is greater than Limit 1, switch heat to
cool at Limit 1, cool to heat at Limit 2. For binary open/close contact, open is a high value (100%), closed is a low
value (0%).
Limit 2 > Limit 1
Mode
Limit
1
Doc: 70-00-0365C, V2.0, 20220523
Subject to alteration
Heat
Cool
Limit
Input
2
© Vector Controls GmbH, Switzerland
TCI-W13, TCI-W23 Universal Controller
A
F
UX
UNCTIONS
Limit 1 > Limit 2
Heat
Mode
Cool
Limit
2
C
ONFIGURATION
Range
Default
0–6
0–1275s
300
per input
per input
Limit
Input
1
0
20
40
Page 20-22