Vector TLC3-FCR-T Engineering Manual

Vector TLC3-FCR-T Engineering Manual

Intelligent fan coil controller

Advertisement

Quick Links

TLC3-FCR-T
Intelligent Fan Coil controller
Features
The PWM control option reduces room temperature
fluctuations and energy consumption
Low power energy consumption: < 1W per unit
Temperature control for 2- pipe fan coil systems.
External sensor or open contact for remote control,
external heat – cool change or auto-changeover on supply
temperature with selectable activation limits
Automatic fan control for three stage fans.
Cost saving option with Economy functionality and set point
limitations
Control for single stage heating, cooling and fan only
operation modes
Password protected programmable user and control
parameters
Setpoint range limitation
o
Access control for setpoints, fan speeds and mode change
o
Access control for heat/cool change and time programs
o
Select your display contents
o
Selectable behavior after return from power failure
o
Temperature display in Celsius or Fahrenheit
Deluxe Version:
Clock and time schedule functions with power failure protection
Blue backlight for LCD
Infrared remote controller option:
With special features for Boost and delayed switching on or off
Applications
Air Only Systems:
Constant Air Volume systems with three stage fans for single or dual duct systems
o
Air/Water Systems:
Fan Coil units for 2-pipe systems
o
radiator control, chilled ceiling
o
Simple individual room control for hotel rooms, meeting rooms, etc.
PWM or On-Off-Control of 2 spring return valves or 3-point on-off or floating control of one 3-point valve.
General Description
The TLC3-FCR-T is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-T features 1 NTC
temperature sensor input, 1 external NTC or open contact input and four binary outputs (Relays).
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-T can be
configured using the standard operation terminal. No special tools or software is required.
Ordering
Item Name
TLC3-FCR-T
TLC3-FCR-T-W01
TLC3-FCR-T-230
TLC3-FCR-T-230-W01
TLC3-FCR-T-D-24
TLC3-FCR-T-D-24-W01
TLC3-FCR-T-D-230
TLC3-FCR-T-D-230-W01
Selection of actuators, fans and sensors
Temperature Sensors: Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-
Tn10-15 as Duct sensor, SRA-Tn10 as Room sensor and SDB-Tn10-15+AMI-10 as immersion sensor.
Binary auxiliary devices: E.g. fans, on/off valves, etc. Do not directly connect devices that exceed switching power.
Observe startup current on inductive loads! Do not connect more than one fan coil unit to one controller.
Doc: 70-00-0200, V3.1 Date: 20160411
Subject to alteration
Item code
Variant
Standard
40-10 0129
Cooling only
40-10 0129-01
Standard
40-10 0114
Cooling only
40-10 0114-01
Deluxe
40-10 0134
Cooling only
40-10 0134-01
Deluxe
40-10 0115
Cooling only
40-10 0115-01
© Vector Controls GmbH, Switzerland
TLC3-FCR-T Engineering Manual
Power
24VAC/DC
Fan coil controller with:
230VAC
1 TI int or ext
3 DO (Relay) Fan control
24VAC/DC
1 DO (Relay) Binary valve control
230VAC
Features
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Vector TLC3-FCR-T

  • Page 1 PWM or On-Off-Control of 2 spring return valves or 3-point on-off or floating control of one 3-point valve. General Description The TLC3-FCR-T is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-T features 1 NTC temperature sensor input, 1 external NTC or open contact input and four binary outputs (Relays).
  • Page 2: Technical Specification

    60 x 50 x 32mm (2.4 x 2.0 x 1.26 in.) Distance for mounting screws: Horizontal and vertical: 45 to 63mm (1.8 to 2.5 in.) Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3: Mounting Location

    Binary output 230V AC: Valve (Heating or cooling) External input: NTC 10kΩ @ 25°C (77°F) or open contact to SGND Signal common: 0 potential for inputs Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    External input for heat / cool auto-change-over missing or damaged. Verify wiring or setup. Steady: Frost protection is active. Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5: Clock Operation

    A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined.  See chapter operation, advanced settings for instructions on how to set the time. Access to time schedules may be disabled with UP-04  Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6: Clock Settings

    Repeatedly pressing the mode button may activate the following operation modes: HEAT, COOL and FAN ONLY. The mode change may be disabled using the UP parameters. Note: The remote controller is currently only available in °C mode. Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7 Setting of user parameters The TLC3-FCR-T is an intelligent controller and can be adapted to fit perfectly into your fan coil application. The control operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.
  • Page 8: Control Configuration

    It is not recommended to use cycle times below 10 minutes as the lifetime of the relays will be shortened with frequent switching. For PWM applications requiring cycle times below 100 seconds we recommend using TLC3-FCR-2 with TRIAC outputs Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9: Input Configuration

    This keeps the fan running until the defined time runs out when switching the unit off or deactivating the valve. The idea is to prevent condensation on the cooling coil or triggering the overheat fuse on electrical reheat devices. Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...
  • Page 10 TLC3-FCR-T Engineering Manual Notes: Doc: 70-00-0200, V3.1 Date: 20160411 © Vector Controls GmbH, Switzerland Page 10 Subject to alteration...