Connecting the concentric fl ue
Assemble the concentric direct vent system according to one of the examples in fi gure
13 to 18 inclusive.
Make sure that all connections are completely gas tight.

Building in the appliance

Remove the front of the casing, if applicable. (See Chapter: DISMANTLING /
ASSEMBLING OF THE GLASS.)
Decide on positions of the convection vents (openings/grids above the fireplace).
The brickwork must be built up around the appliance. In connection with the appliance
expanding during burning: there must be at least ⅛" (3 mm) clearance on either side of
the appliance. Do not build up the brickwork farther than the angle irons/brackets (keep
in mind the thickness of any plastering!).
Do not use masking tape on the appliance when installing and
plastering. Tape can damage the fi nish of the appliance.
The optional mantel iron is intended for supporting the brickwork above the hearth. The
mantel iron must rest on the brickwork on both sides so that upward building is possible.
The brickwork therefore must not rest on the fireplace; there must be approx. ⅛" (3 mm)
clearance in connection with the weight. Put ceramic felt on the top of the mantel iron,
before laying bricks or using other nonfl ammable structural materials.
If using other materials, such as stone or heat-resistant plating, you should follow the
supplier's instructions.
Checking the gas connection
After connection of the gas supply, check once again that all connections are completely
gas tight using soapy water or a leak tester.
Once the fi replace has been fi nished, you can now, fi t the frame with the small door to
the operating unit.
Depending of enclosure: After installation in a new fi replace and/or applying new
cement work, the appliance cannot be used for at least four weeks.
Bellfi res
BUILDING IN THE APPLIANCE
IMPORTANT:
53
Installation instructions