Suggestion, positioning, location
Before connecting up the radiator to the mains
power supply, switch off mains power at the main
circuit breaker.
This electric radiator is a class II double insulated IP24
device, therefore it can be installed in all the rooms of
a house including in safety zones 2 and Out of zone in
bathrooms, but sheltered from water splashes.
The heating device must be installed in such a way
that on-off switches and other control devices cannot
be touched by a person located in a bathtub or in a
0,60 m
This picture is only for your reference. In any case, the product must be installed by a qualified
professional installer, according to applicable standards and directives of the country in which it
is installed.
Locate the heater within minimum distances from
obstacles.
Zone 0
0,60 m
15 cm
50 cm
15 cm
50 cm
15 cm
shower cabinet (in accordance with I.E.E. Wiring Reg-
ulations (BS 7671:2008)).
The radiator must not be located immediately below
a socket-outlet.
The radiator must be installed at least 15cm from any
obstacle (ie shelving, curtains, items of furniture, etc.).
A mean of disconnection mains supply capable of
disconnecting all poles, having a contact separation
of at least 3mm in accordance with local regulations
and installation rules.
Zone 0
0,60 m
No electric heating device.
Zone 2
Electric heating device of class II and
IPX4 protected by a differential circuit
breaker 30mA.
Out of zone
Electric heating device of class I or
II protected by a differential circuit
breaker 30mA.
Installation recommended in the context of using
automatic open window detection and occupancy
detection.
Legend
= The ideal recommended
location
4
Zone 1
2
= Alternative
location