Faults - Possible causes - Solutions

If faults arise in ignition or operations, the burner performs a
"safety stop", which is signalled by the red burner lockout LED.
The display visualises alternately the lockout code and the rela-
tive diagnostic. To reset the start-up conditions, refer to the "Re-
set procedure" indicated in the control box manual supplied.
When the burner starts again, the red LED goes out and the con-
trol box is reset.
Problem
The burner does not start
The burner does not switch on and the
lockout appears
The burner starts and then goes into lock-
out
The burner turns on and then remains in
lockout mode
Once the pre-purging and the safety time
has elapsed, the burner goes into lockout
without the flame appearing
Locks out with flame
The burner continues to repeat the start-
up cycle, without lockout
20169009
Faults - Possible causes - Solutions
Possible cause
No electrical power supply
A limiter or safety control device is open
Flame control lockout
Control box fuse broken
Incorrect electrical wiring
Defective flame control
No gas supply
Mains gas pressure insufficient
Minimum gas pressure switch fails to close Adjust or replace
Air pressure switch in operating position
Flame simulation
Air pressure switch does not switch owing to lack of air pressure:
Air pressure switch is badly adjusted
Pressure switch pressure test point pipe
blocked
Head wrongly adjusted
Defective flame detection circuit
The VR solenoid lets too little gas through Increase it
The VR or VS solenoid valve does not
open
Gas pressure too low
The burner's pilot is not functioning
Firing transformer defective
Incorrect valve or firing transformer con-
nections
Defective control box
A closed valve up-line from the gas train
Air in pipework
The VR solenoid lets too little gas through Increase it
Maximum gas pressure switch intervention Adjust or replace
Defective control box
The gas pressure in the network is near the
value on which the min. gas pressure
switch is adjusted.
The sudden fall in pressure that follows the
opening of the valve causes the temporary
opening of the pressure switch itself imme-
diately the valve closes and the burner
stops.
The pressure starts to increase again, the
pressure switch closes and repeats the
start up cycle. The sequence repeats end-
lessly.
32
GB
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
locks out for a third time, contact the customer
WARNING
service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
Recommended remedy
Close all switches - Check connections
Adjust or replace
Release
Replace it
Check connections
Replace it
Open the manual valves between meter
and train
Contact your gas company
Adjust or replace
Replace the control box
Adjust it or replace it
Clean
Adjust
Replace control box
Replace the coil or the rectifier panel
Increase pressure at regulator
Check
Replace it
Redo them
Replace
Open it
Bleed air
Replace
Reduce the operating pressure of the min.
gas pressure switch.
Replace the gas filter cartridge.