SMA Firmware Data Formats

Four values are extracted from the delivered double word (DWORD) within the corresponding Modbus register. The
values "Major" and "Minor" are contained BCD-coded in bytes 1 and 2. Byte 3 contains the "Build" value (not BCD-
coded). Byte 4 contains the "Release Type" value according to the following table:
Release type
0
1
2
3
4
5
> 5
Example:
Product firmware version:
Values from double word (DWORD):
3.5

Modbus Ports

The following table shows the default setting of the supported network protocols:
Network protocol
TCP
Using free ports
Only use free ports when using another port than 502. The following range is generally available: 49152 to
65535.
You can find more information on occupied ports in the database "Service Name and Transport Protocol Port
Number Registry" at http://www.iana.org/assignments/service-names-port-numbers/service-names-port-
numbers.xml.
Technical Information
Explanation
Revision number of the form 2.3.4.5.
Temperature values are stored in special Modbus registers in degrees Celsius
(°C), in degrees Fahrenheit (°F), or in Kelvin K. The values are commercially
rounded, with one decimal place.
UTC time, in seconds
Data in UTF8 format.
Date/time (Transmission in seconds since 1970-01-01)
Release-type coding
N
E
A
B
R
S
As number
1.05.10.R
Major: 1, Minor: 05, Build: 10, Release type: 4 (Hex: 0x1 0x5 0xA
0x4)
Modbus port
502
Explanation
No revision number
Experimental release
Alpha release
Beta release
Release
Special release
No special interpretation
SMAModbus-ennexOS-TI-en-10