Auxiliary Functions - Vector TCI-W11 Series Manual

Wall mounted universal controller
Hide thumbs Also See for TCI-W11 Series:
Table of Contents

Advertisement

Auxiliary functions

Summer/winter compensation
Parameter
Description
Select compensation input (0= function disabled):
Fu 00
1= 1T, 2= 1H, 3= 1U, 4= 2U
Winter compensation setpoint setback
Fu 01
OFF= shift toward control loop heating set point minimum
ON= shift toward control loop heating set point maximum
Fu 02
Winter compensation lower limit value – end shift
Fu 03
Winter compensation upper limit value – start shift
Summer compensation setpoint setback
Fu 04
OFF= shift toward control loop cooling set point minimum
ON= shift toward control loop cooling set point maximum
Fu 05
Summer compensation lower limit value – start shift
Fu 06
Summer compensation upper limit value – end shift
Fu 07
Show hot/cool symbol while compensation active
Occupied (comfort)/Unoccupied (economy) mode changeover
Fu 08
Select occupied (comfort)/unoccupied (economy) changeover input
(0= disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2U
Fu 09
Unoccupied (economy) activation delay (seconds)
Fu 10
Input limit 1
Fu 11
Input limit 2
Summer/winter compensation changes the set point due to a change in an input value, typically, but not limited to,
an outdoor temperature input. Winter compensation starts when outside temperature drops below the upper limit of
winter compensation (FU03). At maximum winter compensation the actual set point will be equal to the control loop's
maximum heating set point (L02). Summer compensation starts when outside temperature exceeds the lower limit
for summer compensation (FU05). At maximum summer compensation the actual set point will be equal to the
control loop's maximum cooling set point (L04). Activate summer/winter compensation with control loop configuration
parameter(L05).
Set point
Min/max
Use occupied (comfort)/unoccupied (economy) mode changeover with key card switches, occupancy sensors, etc. Set
input limit 1 and 2 with possibilities below. Example: When Limit 2 is greater than Limit 1, switch comfort-to-economy
at the lower value, economy-to-comfort at the higher value. Activate occupied (comfort)/unoccupied (economy)
changeover with loop configuration parameter(L07).
Mode
Doc: 70-00-0158C, V2.0-20220523
Subject to alteration
Winter Compensation – FU01
Summer Compensation – FU04
1L04
1L02
W
1L01
1L03
FU02
Limit 2 > Limit 1
Comfort
Standby
Limit
Limit
1
2
© Vector Controls GmbH, Switzerland
TCI-W11, TCI-W22 Universal Controller
A
UX
FU01-ON
FU04-ON
FU04-OFF
FU01-OFF
FU03
FU05
Comfort
Mode
Standby
Input
F
C
UNCTIONS
ONFIGURATION
Range
0–4
ON/OFF
per input
5°C (41°F)
per input
20°C (68°F)
ON/OFF
per input
35°C (95°F)
per input
40°C (104°F)
ON/OFF
0–4
-1275s
per input
Per input
T [°C,°F],
U[V,mA]
FU06
Limit 1 > Limit 2
Limit
Limit
Input
2
1
Default
0
OFF
ON
OFF
0
300s
10
90
Page 19-22